CPX200NB ALARM CONTROL UNIT – INSTALLER MANUAL  

 

  75 / 116 

 

Battery voltage – voltage of battery in millivolt unit 

8.7.

 

RESTRICTIONS 

8.7.1.

 

SMS and data calls (CSD) 

 

8.7.1.1.

 

Authorized SMS Telephone Numbers 

The user can restrict a remote access to the equipment (via SMS)  from pre-defined 
telephone  numbers.  Created  list  of  telephone  numbers  (up  to  5)  means  that  the 

equipment can be controlled from these telephone numbers only. 
Available options are: 

 

Restrict all: Means no possibility of communication. 

 

Allow all: Means that communication is allowed from any telephone number. 

 

Allow  selected:  Means  that  communication  is  allowed  only  from  these  listed 

telephone numbers. You can define up to 5 telephone numbers. 

When  ‘Allow  selected’  box  is  selected  you  receive  access  to  an  edit  box.  Enter  the 
subsequent numbers in the box and click [Add]  button to move the number to the 
table below. To remove the number from the table, place the cursor in a particular 

number line and click [Remove]. 
“Remove all” option will clear all the numbers from the table. 

Summary of Contents for CPX200NB

Page 1: ...NTROL UNIT CPX200NB Installation and programming manual Version of the manual v1 17 Date of issue 2018 07 31 Firmware version 2 10 0 GPRS transmitter configurator version 1 4 85 3 OSM server version 1...

Page 2: ...not be deemed to be providing any warranties either express or implicit including but not limited to any implied warranties of merchantability or fitness for a particular purpose unless it is require...

Page 3: ...3 KEYPAD INSTALLATION 18 3 6 4 ADDRESSING DEVICES CONNECTED TO THE KEYPAD BUS 18 4 ALARM CONTROL UNIT CONFIGURATION 19 4 1 ZONE BLOCKING 19 4 2 ADDING A NEW USER 19 4 3 USER DELETE 20 4 4 CHANGE OF US...

Page 4: ...CESS 56 8 1 1 PARAMETERS 56 8 1 2 ACCESS POINT NAME 57 8 1 3 PRIMARY SERVER PARAMETERS 58 8 1 4 SECONDARY SERVER PARAMETERS 59 8 1 5 ACCESS 59 8 2 TRANSMISSION 61 8 3 INPUTS OUTPUTS 62 8 3 1 ZONES 62...

Page 5: ...HE BEHAVIOR OF THE SYSTEM IN COMPATIBILITY MODE FOR GRADE 2 93 11 EXTRAS 94 11 1 REMOTE COMMANDS AND CONFIGURABLE PARAMETERS 94 11 1 1 CONFIGURATION PARAMETERS 95 11 1 2 GENERAL COMMANDS 96 11 1 3 COM...

Page 6: ...smitter intended for small and medium sized facilities The central unit is equipped with 3 outputs and 7 zones with the possibility to be divided into 2 partitions Dedicated KP16 LED keypad was design...

Page 7: ...to assign any number of zones to each of them KEYBOARD cooperation with LED keyboard KP16 ability to connect up to three keypads TRANSMISSION Transmission of signals through GPRS SMS module Encryption...

Page 8: ...keypad no sensors connected 120mA 1100mA 18VAC Average current consumption lack of external supply without keypad with keypad fully charged battery no sensors connected established connection with ser...

Page 9: ...h the keypad at the core diameter 0 5mm2 cannot exceed 200m 4 Install detectors and door and window reed relays Connect the installed elements with control unit For sample configuration of zones pleas...

Page 10: ...IM Card The control unit is equipped with integrated GSM GPRS SMS transmitter SIM card with active GPRS transmission is necessary to communicate with the server The card shall be installed in the slot...

Page 11: ...ault admin and instaler code Default admin code is 1111 defoult instaler code is 2222 8 START Button for Battery Activation of Control Unit Without the Mains Power Supply If the control unit is activa...

Page 12: ...UAL 12 116 3 3 DESCRIPTION OF SCREWED CONNECTORS OF THE CONTROL UNIT NOTE Any assembly and installation works shall be carried out with power supply off and battery disconnected Drawing 2 Description...

Page 13: ...lly closed NC or normally open NO as well as with assigned parameters EOL NO or EOL NC using 2 2k resistors or with assigned double parameters DEOL NO or DEOL NC using 1 1k resistors Both resistor typ...

Page 14: ...MANUAL 14 116 3 5 SAMPLE CONNECTION OF A SIGNALLING DEVICE 3 5 1 Internal Signalling Device Without Independent Source of Power Supply Drawing 4 Sample connection of internal signalling device withou...

Page 15: ...ARM CONTROL UNIT INSTALLER MANUAL 15 116 3 5 2 External Signalling Device with Independent Source of Power Supply Drawing 5 Sample connection of external signalling device with independent source of p...

Page 16: ...d control unit operation After first pressing any button the keypad is backlit After a few second idle time backlight gets automatically dimmed In order to make codes easier to remember buttons are ma...

Page 17: ...at the line it is assigned to was disrupted Flashing LED means the zone was interlocked After activating service functions LEDs display data 7 Screwed Connectors The connectors for connecting cables j...

Page 18: ...hould choose the appropriate screws indywidually 5 Connect cables joining the keypad with the alarm control unit Keypad terminals marked KT KR KP KG shall be connected with KT KR KP KG terminals in th...

Page 19: ...confirm blocking of selected zones 3 beeps will confirm the change To cancel the entered changes press 4 2 ADDING A NEW USER You can add a new user code here New codes can be added by the administrat...

Page 20: ...users will be displayed 4 Enter the ID code 1 8 of a user to be deleted and press to confirm or to exit without saving changes 5 Successful deletion of a user will be confirmed with 3 beeps otherwise...

Page 21: ...inistrator code Administrator Code YY Year MM Month DD Day In any moment you can press to exit without saving changes 4 7 RESTORING A DEFAULT USERS CODE To restore a default users code press Pressing...

Page 22: ...perimeter zones assigned to it Partition will arm in the stay mode in following cases 1 Input the user code press and hold the button for 3 seconds 1 2 Input the user cold and press the button If the...

Page 23: ...Error codes 1 Damage or disruption of detector 2 Damage of signalling device or signalling device active 3 Damage of internal connection or sabotage 4 AC power supply damage 5 Battery damage 6 ATS da...

Page 24: ...armed the ARMED LED will be constantly on 5 If the partition arming in the stay mode was selected system will arm immidiately ARMED LED will turn on 6 If partition disarming is selected the relevant...

Page 25: ...that occurred in the system When the function is activated ALARM and PROG LEDs are flashing slowly and all alarms that occurred since last arming are displayed LEDs 1 7 display the information from wh...

Page 26: ...o display more detailed information about sabotage of zones press button 1 Sabotage of zone 1 2 Sabotage of zone 2 7 Sabotage of zone 7 To return to the main fault menu press 2 Fault of outputs 1 3 To...

Page 27: ...zone Example of use walk around the protected object and activate detectors After activate detectors relevant LEDs will go off LEDs that are still on indicate inactive or broken detectors To exit the...

Page 28: ...will generate an alarm2 corresponding to the key Fire alarm Medical alarm Panic alarm burglary Note for the emergency buttons to work it is necessary to be in arm disarm ready mode and wait at least...

Page 29: ...t corresponds to The installer can change the option status as many times as they want When the desired status is set press to confirm or to exit without saving changes Decimal type DEC Service functi...

Page 30: ...it test mode automatically after 5 minutes without pressing the buttons and system will restart 6 3 INSTALLER CODE The installer code can be changed here 3 beeps will confirm the successfully entered...

Page 31: ...ing Instead arm prevention is automatically overridden If option is enabled faults causes arm prevention which can be overridden by user 4 Access to alarm and fault memory requires authorization If th...

Page 32: ...number of option BIT type parameter 1 Users remote management enable when is swiched on You can press any time to exit without saving changes 6 8 ZONES CONFIGURATION The zones can be configured using...

Page 33: ...options BIT type parameter o 1 circuit ignored during arming i e can be violated during partition arming e g delay circuits shall be set to that option o 2 generates alarm when violated after arming...

Page 34: ...3 power failure o 4 ATS failure no communication with receiving server o 5 GSM signal jamming indicator o 6 chirp on arm disarm o 7 chirp on arm disarm and signalling alarm 2 time of output activation...

Page 35: ...es the number of partition from 01 to 02 entering number 00 will change the parameters for both partitions Y number of parameter related to a selected partition 0 complex function the initiation of wh...

Page 36: ...paritions will copy activation deactivation option from the first partition to the second partition Execution of complex function 3009 auto disarming activation deactivation for all paritions will co...

Page 37: ...ommand confirmation there will be digits displayed which represent outputs activated by emergency button Use digits 1 3 to change this setting Functions which configure all three buttons will not chan...

Page 38: ...s refused access to text messages Choice of installer s permissions can be accepted by pressing the button CPX200NB can store up to 10 phone numbers and up to 32 text messages If for any reason the SM...

Page 39: ...PARTITION2 default partitions names they can be changed with the SETNAME command X Y partition states possibile values 0 disarmed 1 armed GETARMED ERROR command rejected by the system Setting the name...

Page 40: ...tion GETNAME PARTITION NR VALUE partition name GETNAME ERROR command rejected by the system Setting the phone number Command syntax XXXX SETTELNUM ID NUMBER Command description Setting the phone numbe...

Page 41: ...k message description GETTELNUM ID NUMBER information about phone number GETTELNUM ERROR command rejected by the system Setting the content of text message Command syntax XXXX SETMESSAGE ID MESSAGE Co...

Page 42: ...ting the content of text message under the pointed index XXXX user code ID index of text possible values 1 to 32 Example 1234 GETMESSAGE 30 Feedback message GETMESSAGE ID MESSAGE or GETMESSAGE ERROR F...

Page 43: ...s Each digit counting from the left represents an index of the phone number first digit for the first phone number second digit for the second number and so on 0 message will not be send to this numbe...

Page 44: ...number assigned to the specified event XXXX user code EVENT a short name of the event possible event names are listed at the end of this chapter Example 1234 GETUSERSMS ARM1 Feedback message GETUSERSM...

Page 45: ...of zones 1 7 ended INPUT1 TAMPER to INPUT7 TAMPER Sabotage of zones 1 7 INPUT1 TAMPEREND to INPUT7 TAMPEREND Sabotage of zones 1 7 ended INPUT1 LOCK to INPUT7 LOCK Bypass of zones 1 7 INPUT1 UNLOCK to...

Page 46: ...d 1 3 KEYPAD1 TAMPEREND to KEYPAD3 TAMPEREND Sabotage of keypad 1 3 ended KEYPAD FIRE BEGIN Fire alarm started KEYPAD HELP BEGIN Help alarm started KEYPAD SILENTALARM BEGIN Panic alarm started KEYPAD...

Page 47: ...gramming SIM card must be inserted before the configuration settings transmission is initiated In this case use either SIM cards with PIN code authorization deactivated or change the PIN code using a...

Page 48: ...rectory where the file was saved then give the file name User can modify the received data In order to be effective the implemented changes must be sent to the equipment 7 3 1 3 File Save If you progr...

Page 49: ...ction is executed through a dedicated programming cable using RS 232 serial port To program the equipment or perform other activities i e read the settings from the equipment change the firmware etc y...

Page 50: ...e e g www ebs pl Enter the port on which analyser will listen to instructions e g 9000 Click Add button to confirm the setting The connection is saved and moved to the table From that moment the progr...

Page 51: ...ntrol unit must accept CSD connections see item 5 5 2 Authorized numbers of GSM modems Programming through CSD connection is possible also when OSM Server system is installed with at least one GSM mod...

Page 52: ...is confirmed with relevant message You can save the data downloaded from the equipment in a file see item 6 3 1 3 and then use it for other devices You can use that function after you define a type an...

Page 53: ...onnection definition window will be displayed The operation is possible using local connection only After the operation is completed the equipment parameters will return to default factory settings 7...

Page 54: ...ect the programming cable or switch the programming device into DEBUG mode Insert SIM card Re connect the power supply The equipment is ready for operation 7 4 2 Remote programming Remote programming...

Page 55: ...he server in Equipment tab it will be marked green Start the software and define the options of the equipment for description please refer to chapter 7 Select Send function The window will appear wher...

Page 56: ...on mode Depending on user s preferences the equipment can operate in one of 4 modes to be selected from a drop list GPRS SMS GPRS transmission TCP IP protocol in standard and in case of problems with...

Page 57: ...s often as in case of GPRS transmission is usually undesirable That parameter allows significant extension of interval between tests time in minutes or disabling that option 8 1 1 5 Telephone number o...

Page 58: ...nication server software is installed e g 89 123 115 8 The address can be given as a server s domain name e g modul gprs com In such a case at least one DNS server address is required 8 1 3 2 Server p...

Page 59: ...fter which the equipment will retry to connect with a server in case the previous attempt was unsuccessful 8 1 4 4 Number of attempts of establishing connection with a server You can define how many t...

Page 60: ...be changed via OSM Server Console In such case please send following Custom command SETPARAM 3 1 new_code where new_code should contain from 4 up to 7 digits 8 1 5 3 SIM Card PIN code Since the equipm...

Page 61: ...maximum transmission security the data transmitted are encrypted using AES The option can be used for both GPRS and SMS transmissions In case encrypted transmission was selected you can enter own dat...

Page 62: ...configuration types are available NC NO EOL NC EOL NO DEOL NC DEOL NO NC type input must be closed for the whole time Line interruption causes its induction NO type input remains open It activates whe...

Page 63: ...ad display or sounding 24h fire works like 24h burglary Perimeter This zone will be armed immidiately after arm command Violation of this zone will raise the alarm even during the exit time countdown...

Page 64: ...unction 50 block inputs 8 3 1 4 Sensitivity That parameter defines a minimum time the change must maintain at the particular zone to be detected by a transmitter Default factory setting of the paramet...

Page 65: ...CPX200NB ALARM CONTROL UNIT INSTALLER MANUAL 65 116 8 3 1 7 Ignore during arming Zone can be violated during partition arming e g delay circuits shall be set to that option...

Page 66: ...turn will be ignored 8 3 2 2 Entry Exit The parameter allows switching off the indication of time for entry exit displayed by KP16 keypad 8 3 2 3 Time for exit It is time for leaving the partition Ass...

Page 67: ...e remote control and remote command For each input line is available Interlocking after time for exit option If this option is active in the case of arming with violated zone after time for exit will...

Page 68: ...nication loss Output is activated when information transmission to server is not possible GSM jamming indicator Output is activated when jamming GSM Chirp The output is activated when arming 1 chirp o...

Page 69: ...8 3 3 4 Bistable The parameter allows set bistable mode of the output In this mode the output will be switched on for the duration of the state specified in the Output Type If you set the output type...

Page 70: ...outpus has the reminder of it s function chosen in the Outputs tab 8 4 SYSTEM OPTIONS 8 4 1 Show failures history with SYSTEM diode Selecting this option indicates that a fault occurred in the system...

Page 71: ...unter of invalid codes will be reset after a correct code is entered e g after entering invalid code two times This option must be enabled in order to comply with EN 50131 standard requirements for Gr...

Page 72: ...the Accept changes button and then upload the configuration to the device When uploading a configuration Write users option must be selected in the writing options Users configuration changes can be...

Page 73: ...Clear button to remove all checked signals Press Reverse to reverse the check into the opposite ones 8 6 1 2 SMS ON OFF In these columns you can check which signals are to be reported to the monitori...

Page 74: ...ents to monitoring station via GPRS SMS The data may become valuable information about device s work conditions though it may increase amount of bytes sent through GSM network It is possible to define...

Page 75: ...y Available options are Restrict all Means no possibility of communication Allow all Means that communication is allowed from any telephone number Allow selected Means that communication is allowed on...

Page 76: ...m these listed telephone numbers You can define up to 5 numbers When Allow selected box is checked you receive access to an edit box Enter the subsequent numbers in the box and click Add button to mov...

Page 77: ...important mainly for economic reasons Check the Activate SMS restrictions check box to activate the access to information groups subject to restrictions SMS tests to server SMS events sent to server...

Page 78: ...8 7 2 Remote commands 8 7 2 1 Users remote management enable Selecting this option allows you to remotely configure user accounts...

Page 79: ...y users about occurrence of certain events by text message Before sending the message may occur an additional attempt a voice call see item 8 8 4 Options In order to add user s number to the notificat...

Page 80: ...e has to typed in the Messages tab These messages can be later assigned to specific events in the Events tab Before sending the message may occur an additional attempt a voice call see item 8 8 4 Opti...

Page 81: ...e Message column select one of the messages defined before To assign a number to an event a corresponding column from Num 1 to Num 10 has to be checked From now on whenever this event occurs a text co...

Page 82: ...call the device sends an SMS message Sending a message to the first user the first defined phone number is followed by an attempt to call the next user and send a message And so on A voice call to a s...

Page 83: ...CPX200NB ALARM CONTROL UNIT INSTALLER MANUAL 83 116...

Page 84: ...one number can be composed of an empty sequence which means it is applicable to any telephone number Rules are processed in accordance with a pre defined sequence from the beginning to the end i e the...

Page 85: ...ers defining the equipment s response after leaving GSM network You can define after what time from the moment the connection was lost the equipment shall initiate activities aiming at its restoration...

Page 86: ...nd is defined in minutes Then define what activity shall be initiated by the equipment Select by checking an appropriate box at the response description Modem reset Device reset In case the equipment...

Page 87: ...ow the equipment will operate under the control of a new firmware NOTE The firmware update procedure shall be carried out with special care as improperly performed operation can prevent the correct op...

Page 88: ...quipment The control unit has an event log memory where about 5 thousand technical events can be recorded You can review the events history via GPRS and RS232 connection In the second situation first...

Page 89: ...CPX200NB ALARM CONTROL UNIT INSTALLER MANUAL 89 116...

Page 90: ...ashing green LED 1 8 blinks The operation mode of the equipment is indicated by green LED which goes on for 2 seconds after the range is indicated In case the LED does not go on for 2 seconds after th...

Page 91: ...otloader remains in the equipment and repeated equipment programming is possible Description LEDs OK green ERROR red STATUS yellow No software in the equipment Software update Decryption of firmware r...

Page 92: ...cted to the control panel The battery capacity should be sufficient to operate the system without a power supply for 12 hours In the GPRS Transmitters Configurator see item 8 4 or in the service menu...

Page 93: ...rms is available only after user code has been entered information about alarms memory is available only after user code has been entered information about failures is available only after user code h...

Page 94: ...bles below The newly configured parameter will be taken into account when the device will need to use it there is no need to restart the unit However there are parameters changes to which will be dete...

Page 95: ...Format PW password Limitations Data length to 31 characters can be changed by ATS only Description Sets the password for APN 11 1 1 4 SERVER Format SERVER server_address Limitations Data length to 31...

Page 96: ...e is given in minutes 11 1 1 8 DT Format DT YY MM DD hh mm Limitations Data length of 14 characters can be changed only by ATS or Administrator Description Sets date and hour 11 1 2 General commands T...

Page 97: ...nd GPRS network when you restart the device and modem 11 1 2 4 DESC Format DESC Limitations Can be executed by ATS only Description Returns a string with a description of the device containing firmwar...

Page 98: ...1 0 switch on output 1 in bistable state OUT 3 1 10 switch on output 3 for 10 seconds 11 1 2 7 FLUSH Format FLUSH x Limitations x is equal to 0 or 1 possible to execution only by ATS Description For...

Page 99: ...uts means the current status of outputs It is a bit vector where bit 1 counting from 0 means the output 1 bit 2 the output 2 and bit 3 the output 3 If the output is enabled the bit is set Battery_volt...

Page 100: ...iption Gets a list of users defined in the device adminPassword is the system administrator password The command returns CPGETUSERS id name partitions Where id is the user number name is the text user...

Page 101: ...ether a user with the specified code exists Password is the password of the user id is the user number partitions are the partitions to which the user is authorized bit 0 corresponds to the partition...

Page 102: ...r of the user whose authorizations are changed the partitions is the bit vector with the partitions to which the user should have the authorization bit 0 corresponds to the partition 1 bit 1 to the pa...

Page 103: ...user s password Id is the user identifier whose password is changed the password is his new password and the adminPassword is the system administrator password The command returns CPSETUSERPASSWORD E...

Page 104: ...uthorization bit 0 corresponds to the partition 1 bit 1 to the partition 2 password is the password of newly created user and adminPassword is the the system administrator password The command returns...

Page 105: ...ommand is executed by ATS specify adminPassword Description Delete the user Id is the user number adminPassword is the system administrator password The command returns CPDELUSER EOK id If the user is...

Page 106: ...administrator The command is designed to give the ability to remotely restore the password by monitoring station employees if it is forgotten NewPassword is the new password of the main user The comm...

Page 107: ...ponding to the zone 1 bit 7 corresponds to the zone 7 otherAlarmHistory a bit vector indicating the additional alarm memory from the last arming Bit 1 counting from 0 corresponding to the tamper keypa...

Page 108: ...ireless detectors and control panel Bit 1 counting from 0 corresponds to the zone 1 bit 7 corresponds to the zone 7 In CPX200NB system this field is set to 0 zonesPowerFailures is a bit vector indicat...

Page 109: ...failures of power supply outputs Bit 0 means the output KPOUT bit 1 means the output AUX1 bit 2 means the output AUX2 powerInFailures is a bit vector informing about the failures of power supply Bit...

Page 110: ...ctor is optional It means that partitions in the bit vector will be armed in stay mode It is not allowed to change arm mode of an already armed partition system will reject an attempt of arming in sta...

Page 111: ...al to zero has no sense since it does not change anything if the partitions is 0 the user s password is not checked and the status returned by the command is equal to EOK Password is the code of the u...

Page 112: ...nts to block Bit 1 counting from 0 means the zone 1 Sending a command with the argument of zones equal to 0 has no sense since it does not change anything Password is the system administrator or user...

Page 113: ...it vector indicating the zones which one wants to unblock Bit 1 counting from 0 means the zone 1 Sending the commands with the argument of zones equal to 0 has no sense since it does not change anythi...

Page 114: ...is the system administrator or user password Returns a list of zones assigned to the partition in the format CPPARTITIONSGETZONES P1Zones P2Zones Where P1Zones P2Zones are the bit vectors indicating...

Page 115: ...ystem admiinistrator or user password Returns a list of outputs assigned to the partition in the format CPPARTITIONSGETOUTPUTS P1Outputs P2Outputs Where P1Outputs P2OUtputs are the bit vectors indicat...

Page 116: ...ion 29 10 2015 i1 9 2 2 0 Call before sending SMS option updated 09 11 2015 i1 10 2 3 1 Updated 24h tamper zone description function Reset to default setting description and information about stay awa...