80
Typ EP 501
Start-Up
23.3.7.
FILTER
– Filtering of the process actual value input
The filter is valid for all process actual value types and has a low pass behavior (PT1).
Factory setting: 0
Operating structure:
Adjustment range: 0 ... 9
EXIT
Input value
ENTER
INPUT
OK
ESC
PID.PARAMETER
DBND 1.0 %
FILTER 0
Figure 39:
Operating structure FILTER; filtering of the process actual value input
Setting.the.filter.effect.in.10.stages
Setting
Corresponds to cut-off frequency (Hz)
Effect
0
10
Lowest filter effect
1
5
2
2
3
1
4
0.5
5
0.2
6
0.1
7
0.07
8
0.05
9
0.03
Largest filter effect
Table 37:
Setting the filter effect
On page 204 you will find a table for entering your set parameters.