Start-Up
21.2.
X.TUNE
– Automatic adjustment of the positioner
WARNING!
Danger.due.to.the.valve.position.changing.when.the.
X.TUNE
.function.is.run.
When the
X.TUNE
function is run under operating pressure, there is an acute risk of injury.
▶
Never run X.TUNE
while the process is running.
▶
Secure system against unintentional activation.
NOTE!.
An.incorrect.supply.pressure.or.incorrectly.connected.operating.medium.pressure.may.cause.the..
controller.to.be.wrongly.adjusted.
▶
Run X.TUNE
in.each.case.
at the supply pressure available in subsequent operation (= pneumatic auxiliary power).
• Run the
X.TUNE
function preferably
without
operating medium pressure to exclude interference due to flow
forces.
The following functions are actuated automatically:
• Adjustment of the sensor signal to the (physical) stroke of the actuator used.
• Determination of parameters of the PWM signals to control the solenoid valves integrated in Type EP 501 /
EP 501 C.
• Adjustment of the controller parameters for the positioner. Optimization occurs according to the criteria of the
shortest possible transient time without overshoots.
Procedure:
Key
Action
Description
MENU
Press
for approx. 3 s
Switching from process level
setting level.
/
Select
X.TUNE
RUN
Hold down
as long as countdown (5 ...) is
running
While the automatic adjustment is running, messages on the
progress of the
X.TUNE
(e.g.
"TUNE #1...."
) are indicated on the display.
When the automatic adjustment ends, the message
"X.TUNE READY"
is indicated.
Press any key
Return to the main menu (MAIN).
EXIT
Press
Switching from setting level
process level.
Table 26:
Automatic adjustment of X.TUNE
To stop
X.TUNE
, press the left or right selection key
STOP
.