132
Typ EP 501
Auxiliary functions
24.2.22.4. Activation of diagnosis functions
In the
ADD.DIAGNOSE
menu several diagnosis functions are activated and incorporated into the
DIAGNOSE
main menu.
Activatable diagnosis functions:
HISTOGRAM
Graphical display of the dwell time density and movement range.
SERVICE.TIME
Operating-hours counter
TRAVEL.ACCU
Path accumulator
CYCLE.COUNTER
Direction reversal counter
TEMP.CHECK
Temperature monitor
STROKE.CHECK
Monitoring of the mechanical end positions in the armature
PV.MONITOR
Process actual value monitoring (only for Type EP 501 C, process control)
POS.MONITOR
Position monitoring
Table 67:
ADD.DIAGNOSE; overview of diagnosis functions
The exact description can be found in Chapter “24.2.22.6. Description of the diagnosis functions”
ADD.DIAGNOSE
.-.Activating.diagnosis.functions:
Key
Action
Description
MENU
Press
for approx. 3 s
Switching from process level
setting level.
/
Select
DIAGNOSE
(To do this, the
DIAGNOSE
auxiliary function must already have
been activated by incorporation into the main menu (MAIN)).
ENTER
Press
The submenus are displayed.
/
Select
ADD.DIAGNOSE
ENTER
Press
The other diagnosis functions are displayed.
/
Select required diagnosis
function
ENTER
Press
The required diagnosis function is now marked by a cross .
either
/
Select further diagnosis
functions
Keep repeating until all required diagnosis functions have been
marked with a cross .
ENTER
Press
or
EXIT
Press
Acknowledgment and simultaneous return to the
DIAGNOSE
main
menu.
The marked diagnosis functions have been activated and the setting
menus are now in the
DIAGNOSE
main menu.
Table 68:
Activation of diagnosis functions
english