2. PROPER USE

The device is exclusively designed as a built-in device for conveying
air according to its technical data.
Any other usage above and beyond this does not conform with the
intended purpose and constitutes misuse of the device.
Customer equipment must be capable of withstanding the mechanical
and thermal stresses that can arise from this product. This applies for the
entire service life of the equipment in which this product is installed.

Proper use also includes:

Use the device in power systems with earthed neutral (TN/TT power
systems) only.

Only using the device in stationary systems.

Carrying out all maintenance.

Moving air with a density of 1.2 kg/m³.

Using the device in accordance with the permitted ambient
temperature, see chapter 3.5 Transport and storage conditions and
chapter 3.2 Nominal data.

Operating the device with all protective features in place.

Minding the operating instructions.

Improper use

Using the device in the following ways is particularly prohibited and
may cause hazards:

Operating the device with an imbalance, e.g. caused by dirt deposits
or icing.

Operation in medical equipment with a life-sustaining or lifesaving
function.

Operation with external vibrations.

Moving solids content in flow medium.

Painting the device

Connections (e.g. screws) coming loose during operation.

Opening the terminal box during operation.

Moving air that contains abrasive particles.

Moving highly corrosive air, e.g. salt spray mist. Exceptions are
devices that are intended for salt spray mist and protected accordingly.

Moving air that contains dust pollution, e.g. suctioning off saw dust.

Operating the device close to flammable materials or components.

Operating the device in an explosive atmosphere.

Using the device as a safety component or for taking on safety-
related functions.

Operation with completely or partially disassembled or modified
protective features.

In addition, all application options that are not listed under proper use.

Item no. 53034-5-9970 · ENG · Revision 84452 · Release 2015-01-12 · Page 3 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for R3G500-RA34-11

Page 1: ...o install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device Observe the following when working on the unit Do not make any modifications additions or conversions to the device without the approval of ebm papst 1 ...

Page 2: ... on the system machine wait until all parts have come to a standstill DANGER Flying parts Missing safety devices may cause balancing weights or broken fan blades to be ejected at high speeds causing bodily harm Take appropriate safety measures WARNING Rotating device Long hair loose items of clothing and jewellery could become entangled and pulled into the device You could be injured Do not wear a...

Page 3: ...ice in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sustaining or lifesaving function Operation with external vibrations Moving solids content in flow medium Painting the device Connections e g screws coming loose during operation Opening the terminal box du...

Page 4: ...zzle 50901 2 2943 not included in scope of delivery 2 Depth of screw max 25 mm 3 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 4 Tightening torque 3 5 0 5 Nm Item no 53034 5 9970 ENG Revision 84452 Release 2015 01 12 Page 4 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 5: ... locked rotor protection Protection class I if protective earth is connected by customer Product conforming to standard EN 61800 5 1 CE Approval C22 2 Nr 77 CAN CSA E60730 1 UL 1004 7 60730 For cyclic speed loads note that the rotating parts of the device are designed for maximum one million load cycles If you have specific questions contact ebm papst for support 3 4 Mounting data Secure the mount...

Page 6: ...s at the cable end on the customers side and can damage the device Make sure that the cable end is connected in a dry environment Connect the device only to circuits that can be switched off using an all pole disconnecting switch 4 2 1 Prerequisites Check whether the data on the type plate agree with the connection data Before connecting the device ensure that the supply voltage matches the operat...

Page 7: ... drawing Fig 1 Recommended stripping lengths in mm inside the terminal box Legend CL control lines 4 3 2 Connecting cables with terminals WARNING Terminals and connections have voltage even with a unit that is shut off Electric shock Wait five minutes after disconnecting the voltage at all poles before opening the device Remove the cap from the screwed cable gland Remove the cap only in those plac...

Page 8: ...r set 2 PWM controlling Fan device adress 1 Max PWM 100 Min PWM 5 1 Save set value to EEPROM Yes Set value control Analogue linear Control function parameter set 1 Positive heating Control function parameter set 2 Positive heating Item no 53034 5 9970 ENG Revision 84452 Release 2015 01 12 Page 8 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 1...

Page 9: ...en pin or applied voltage 5 50 VDC disabling bridge to GND or applied voltage 1 VDC reset function triggers software reset after a level change to 1 VDC SELV KL 3 8 Din2 Digital input 2 parameter set switch 1 2 according to EEPROM setting the valid used parameter set can be selected via bus or via digital input DIN2 Parameter set 1 open pin or applied voltage 5 50 VDC Parameter set 2 bridge to GND...

Page 10: ...e fan for foreign objects and remove any that are found Apply the nominal voltage to the voltage supply Start the device by changing the input signal 4 8 Switching off the device Switching off the device during operation Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Switching off the device for maintenance work Switch off th...

Page 11: ...e Switch off de energise and remove mechanical blockage Mains supply voltage faulty Check mains supply voltage restore power supply Important The error message resets automatically The device starts up again automatically without advance warning Faulty connection De energise correct connection see connection diagram Motor winding broken Replace device Insufficient cooling Improve cooling Let the d...

Page 12: ...inst accidental contact for damage and to ensure that it is intact Visual inspection At least every 6 months Repair or replacement of the device Check the device for damage to blades and housing Visual inspection At least every 6 months Replacement of the device Mounting the connection lines Visual inspection At least every 6 months Fasten Check the insulation of the wires for damage Visual inspec...

Reviews: