Operating Instructions 

LMA-1200 “

DEFLECTOMETER” Series 

Single Channel – Dual Output – Inductive Loop Vehicle Detectors 

 

1.

 

Connect to proper source voltage 

Verify source voltage before applying power.  The “Pin Assignment” side label indicates the input power required for each model and indicates either Fail Safe operation 

or Fail Secure operation. 

MODELS 

12 VDC to 24 VDC or 24 VAC 

120 VAC 

240 VAC 

Fail Safe 

Fail Secure 

LMA-1200-LV 

● 

 

 

 

 

LMA-1200-120  

 

 

 

 

LMA-1200-240  

 

 

 

 

LMA-1200S-LV 

 

 

 

 

 

LMA-1200S-120  

 

 

 

 

LMA-1200S-240  

 

 

 

 

 

 

FAIL SAFE OPERATION 

FAIL SECURE OPERATION 

OUTPUT RELAY 

POWER FAILURE 

LOOP FAILURE 

POWER FAILURE 

LOOP FAILURE 

CALL Output 

CALL Output 

No Output 

No Output 

No Output 

No Output 

No Output 

No Output 

 

 

2.

 

DEFLECTOMETER

 Indications 

STATUS 

DEFLECTOMETER 

0, 1, 2, 3, 

4, 5, 6

, 7, 8, 9 

Sensitivity Meter (4, 

5

 & 6 = Optimum Sensitivity Setting for Loop & Lead-in Network) 

2-Second 

D

elay Timing 

0, 2, 5 or 10 Second 

E

xtension Timing 

Current “Real Time” Loop 

F

ailure 

 
 

3.

 

LED Indications 

STATUS 

POWER LED 

OUTPUT A LED 

OUTPUT B LED 

LOOP FAULT LED 

OFF 

No Power 

Output OFF 

Output OFF 

Loop Good 

ON 

Normal Power 

Output ON 

Output ON 

N/A 

2 Hz Flash  

N/A 

2-Second Delay Timing 

2-Second Delay Timing 

N/A 

4 Hz Flash 

N/A 

0, 2, 5, or 10 Second  

Extension Timing 

0, 2, 5, or 10 Second  

Extension Timing 

N/A 

1 Flash 

Insufficient Line 

Power 

“Real Time” Open Loop 

“Real Time” Open Loop 

“Real Time” Open Loop if Outputs A & B are flashing.   

“Prior” Open Loop if Outputs A & B are not flashing. 

2 Flashes 

N/A 

“Real Time” Shorted Loop 

“Real Time” Shorted Loop 

“Real Time” Shorted Loop if Outputs A & B are flashing. 

“Prior” Shorted Loop if Outputs A & B are not flashing. 

3 Flashes 

N/A 

“Real Time” 25% Inductance 

Change 

“Real Time” 25% Inductance 

Change 

“Real Time” 25% Change In Inductance if Outputs A & B are flashing. 

“Prior” 25% Change In Inductance if Outputs A & B are not flashing. 

 
 

4.

 

Rear Panel DIP Switches and Rotary Switch 

 

2-Position DIP Switch – Loop Frequency 

 

SWITCH 

LO 

MEDIUM – LO 

MEDIUM – HIGH 

HIGH 

FACTORY DEFAULT 

ON OFF ON OFF OFF 

ON  ON  OFF OFF OFF 

 

Loop Frequency (DIPS 1 & 2) 

is controlled by the rear panel 2-Position DIP switch.  On occasion, loops are placed in close proximity; it is necessary to select a different 

frequency level for each loop to avoid loop interference (crosstalk).  Four (4) frequencies are selectable, HIGH being the factory default. Press reset after changing sensitivity 

setting. 

 
 

8-Position DIP Switch - Detector Parameter Options 

 

SWITCH ON 

OFF 

FACTORY 

DEFAULT 

Sensitivity Boost 

No Sensitivity Boost 

OFF 

Output A – Limited Presence 

Output A – Infinite Presence 

OFF 

2-Second Delay Timing 

No 2-Second Delay Timing 

OFF 

OFF 

See “Extension Timing” Table Below (Switches 4 & 5) 

OFF 

OFF 

See “Output B Relay Configurations” Table Below (Switches 6 & 7) 

OFF 

8 Reserved 

N/A 

 

Extension Timing (Switches 4 & 5) 

 

SWITCH 

0-Seconds 2-Seconds 5-Seconds 10-Seconds 

4 0FF 

ON 

OFF 

ON 

5 0FF 

OFF 

ON 

ON 

 

 

 

Output “B” Relay Configurations (Switches 6 & 7) 

 

SWITCH 

Pulse On Entry 

Pulse On Exit 

Presence (Duplicates Output A) 

Fault Output 

6 0FF 

OFF 

ON 

ON 

7 0FF 

ON 

OFF 

ON 