5 Installation
5.3 Interfaces
Touch display XV-102
10/2020 MN04802004Z-EN
Eaton.com
37
5.3.8.3
POW/AUX (power supply for SmartWire-DT)
The POW/AUX interface is
not
galvanically isolated.
The following power supplies are required for a SmartWire-DT network:
Supply voltage POW:
The device supply voltage for the electronics of the downstream SmartWire-DT slaves (15 VDC)
is generated from the 24 V DC supply voltage applied to the POW connection.
Supply voltage AUX:
If there are any contactors or motor starters in the SmartWire-DT topology, a 24 V DC voltage AUX
must be additionally supplied as a control voltage for the contactor coils.
Additional properties of the required power supply, see chapter 9.5.2 SmartWire-DT Master,
Wiring
WAGO plug connector, Art no. 734-104 is supplied with the device.
Tab. 13 Plug connection configuration
Observe the following when preparing the wiring of the plug connector:
Tab. 14 Terminating the wiring with the plug connector
External overcurrent and short-circuit protective device, implemented with a miniature circuit-
breaker or a fuse, is required for U
AUX
.
Fig.. 19 POW/AUX power supply interface
Fig.. 20 WAGO plug connector (view from wiring side)
Connection
Configuration
+24 V DC POW
Supply voltage U
Pow
+24 VDC
0 V POW
Supply voltage U
Pow
0 V
+24 V DC AUX
Supply voltage U
Aux
+24 VDC
0 V AUX
Supply voltage U
Aux
0 V
Terminating the wiring with the plug connector
Terminal type:
spring-cage terminal
Connectable conductor, solid 0.2…1.5 mm
2
(AWG24…16)
Strip length
6…7 mm
0 V AUX
+24 VDC AUX
0 V POW
+24 VDC POW