5 Implementation of EtherNet/IP
5.3 VSC-Vendor Specific Classes
106
XI/ON: XNE-GWBR-2ETH-IP
09/2011 MN05002007Z-EN
www.eaton.com
5.3.14
Counter module class (VSC112)
This Class contains all information and parameters concerning the counter module.
Object instance
Two different operating modes can be selected for the counter module: counter mode and
measurement mode. Different attributes are supported depending on the operating mode
selected, meaning, with certain attributes the operating mode has to be defined. The
operating mode is determined in attribute 113.
Note
Please refer to Chapter 5.3.1 Class instance of the VSC, Page 76, for the description
of the class instances for VSC.
Table 55:
Object instance
Attr.
no.
dec.
(hex.)
Attribute name
G
et/
S
et
Type
Description
100
(64h)
Max object attri-
bute
G
USINT
Contains the number of the last object attri-
bute to be implemented.
101
(65h)
Module present
G
BOOL
0 = module missing, base module without
electronic module.
1 = module is plugged
102
(66h)
Terminal slot
number
G
USINT
The slot number of the base module
belonging to the module (base module to
the right of the gateway = No. 1).
Corresponds to the respective Instance
Number within the TERMINAL SLOT
CLASS.
103
(67h)
Module ID
G
DWORD
Contains the module ID.
104
(68h)
Module order
number
G
UDINT
Contains the ident number of the module.
105
(69h)
Module order
name
G
SHORT
STRING
Contains the name of the module, for
example, "XN-1CNT-24VDC".
106
(6Ah)
Module revision
number
G
USINT
Contains the revision number of the module
firmware.
107
(6Bh)
Module type ID
G
ENUM
USINT
Describes the module type: see attribute
107 (6Bh) on page 86
108
(6Ch)
Module
command inter-
face
G/S
ARRAY
The control interface of the XI/ON
module.
ARRAY OF:
BYTE: Control byte sequence
109
(6Dh
Module response
interface
G
ARRAY
Response interface of the XI/ON module.
ARRAY OF:
BYTE: Response-byte sequence