8 Station variants
8.6 CAN objects for station variants
Gateway XN-312-GW-CAN 06/16 MN050003-DE
www.eaton.eu
367
Design of the data bytes:
8.6.3 Module list (internal) (Object 0x4007)
Object 0x4007 is addressed exclusively from the IEC library. The module list
is used to tell the gateway what the full configuration specified by the PLC is.
The gateway then uses this information together with the bitmask for the
nodes that are present in order to identify physically missing nodes and sub-
stitute them when dealing with the field bus.
Subindex 0 contains the number of XN300 slice modules in the full configura-
tion, while subindexes 1 to 32 contain the module ID for the corresponding
module in the full configuration.
Feature
Description / Value
EDS
Type name
INTERNAL_CS_MC
[4006]
Parameter name=INTERNAL_CS_MC
ObjectType=0x7
DataType=0x0007
AccessType=rw
PDOMapping=0
DefaultValue=0
Description
NTERNAL_CS_MC
Object Code
ARRAY
Mapping
SDO
Default
Data type
UNSIGNED32
Sub index
01 … FE
hex
Access
rw
Default value
0000
hex
Byte 0:
Sub index
1
≦
n
≦
254
B7
B6
B5
B4
B3
B2
B1
B0
MSB
LSB