7.21.17 Output Channel Configuration (Object 0x51B1)
Object 0x51B1 can be used to configure the output channels. It is used to
define which current should correspond to the current output value based on
the selected output range.
Design of the data bytes:
Byte 0:
Feature
Description / Value
EDS
Name
OutputChannelConfig
[MxSubExt51B1]
ParameterName=OutputChannelConfig
ObjectType=0x7
DataType=0x0005
AccessType=rw
PDOMapping=0
DefaultValue=0xF0
Count=1
Description
Output Channel Configuration
Object Code
ARRAY
Mapping
SDO
Data type
UNSIGNED8
Sub index
01 … FE
hex
Access
rw
Default value
F0
hex
1 Byte
Byte 0:
Sub index
1
≦
n
≦
254
B15
B14
B13
B12
B11
B10
B9
B8
B7
B6
B5
B4
B3
B2
B1
B0
MSB
LSB
Data bit
Designation
Description
Bit 1
Bit 0
0
0
Channel 1
Output range 0…20mA
0
1
–
1
0
–
1
1
Output disabled
Data bit
Designation
Description
Bit 3
Bit 2
0
0
Channel 2
Output range 0…20mA
0
1
–
1
0
–
1
1
Output disabled
Data bit
Designation
Description
4 – 7
reserved
Summary of Contents for XN-312-GW-CAN
Page 1: ...Manual CANopen Gateway XN 312 GW CAN 06 16 MN050003 EN ...
Page 4: ...II ...
Page 14: ...10 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton com ...
Page 374: ...9 What Happens If 370 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...
Page 388: ...384 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...