![Eaton XN-312-GW-CAN Manual Download Page 268](http://html1.mh-extra.com/html/eaton/xn-312-gw-can/xn-312-gw-can_manual_3796240268.webp)
7 Product-specific CAN objects XN300 slice modules
7.20 XN-322-8AIO-U2
264
Gateway XN-312-GW-CAN
06/16 MN050003-EN www.eaton.eu
7.20.15 Analog Input Selection (Object 0x50B0)
Object 0x50B0 must be used to configure the channels' measuring method.
Design of the data bytes:
Byte 0:
Byte 1:
Feature
Description / Value
EDS
Name
Analog Input Selection
[MxSubExt50B0
ParameterName=AnalogInputSelection
ObjectType=0x7
DataType=0x0006
AccessType=rw
PDOMapping=0
Count=1
Description
AnalogInputSelection
Object Code
ARRAY
Mapping
SDO
Data type
UNSIGNED16
Sub index
01 … FE
hex
Access
rw
Default value
0000
hex
1 Byte
Byte 0:
Sub index
1
≦
n
≦
254
B15
B14
B13
B12
B11
B10
B9
B8
B7
B6
B5
B4
B3
B2
B1
B0
MSB
LSB
Data bit
Desig-
nation
Description
0
Channel
1
0 = Differential measurement
1 = AI1-grounded measurement
1
Channel
2
0 = Differential measurement
1 = AI2-grounded measurement
2
Channel
3
0 = Differential measurement
1 = AI3-grounded measurement
3
Channel
4
0 = Differential measurement
1 = AI4-grounded measurement
4 – 7
reserved
Data bit
Desig-
nation
Description
8 – 15
reserved
Summary of Contents for XN-312-GW-CAN
Page 1: ...Manual CANopen Gateway XN 312 GW CAN 06 16 MN050003 EN ...
Page 4: ...II ...
Page 14: ...10 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton com ...
Page 374: ...9 What Happens If 370 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...
Page 388: ...384 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...