background image

5

Lock 
Anchor B

Lock 

Anchor A

EATON  CORPORATION

  

www.eaton.com.cn/electrical

Instruction Booklet IB

Effective January 2017

XAP Series Busduct

Storage, Installation, and Maintenance

Tap-off Unit Installation

Phase sequence shall be made according to field application require-

ments and construction drawings.

Remove the bolts on the busduct socket cover and open the socket 

protection cover. (See Figure 16).

Open the tap-off unit door. Open Lock Anchor A and B. Then, aim at the 

slot in the socket, and insert in the unit smoothly until the unit bottom is 

closely contacted with the cover (PE pin shall contact the housing first to 

ensure safe grounding). Move the two lock anchors of A and B inwards 

to lock up busduct cover (Figure 19). When Lock Anchor A and B are in 

place, close the unit door and tighten the bolts.

Note: 

When Lock Anchor A and B are in place, it means they are vertical 

to the cover plate and in parallel to the side of the tap-off unit.

Figure 16. Socket

Figure 17. Tap-off Unit Installation

1. After the Tap-off unit is installed onto the busduct, fasten the cable to 

its support in the case that the unit is connected to devices with 

cable, to avoid movement.

2. Tap-off unit shall not be burdened with load directly. Loads at the rear 

end shall be fastened onto the busduct or other fixed positions in 

accordance with regulations.

3. When not plugging in busduct, socket protection cover shall not be 

opened. Otherwise, it will influence the protection degree of 

busduct system.

Busduct Joint Clearances

Busduct joint sections may not fall within walls or floors. Figures 13 

through 15 illustrate the minimum clearances required as measured 

from the center-line of the joint to the wall, floor and ceiling.

Note: 

Busduct joints on outdoor rated busduct should have a minimum 

of 10 in. (254 mm) clearance on either side of walls.

Figure 13. Minimum Outdoor Joint Clearances

Note:

 Busduct joints on Indoor rated busducts should have a minimum 

of 8 in. (203.2 mm) clearance on either side of walls.

Figure 14. Minimum Indoor Joint Clearances

Note:

 Busduct joints on vertically mounted busduct should have a 

minimum of 8 in. (203.2 mm) clearance before ceilings and a minimum 

of 16 in. (406.4 mm) clearance above floors or curbs if used.

Figure 15. Minimum Floor/Ceiling Joint Clearances.

 WARNING

WHEN UNPLUGGING TAP-OFF UNITS, DISCONNECT LOADS. BEFORE 
BUSDUCT SYSTEM POWERS ON, LEAD WIRES OF ALL TAP-OFF UNITS 
SHALL BE CONNECTED TO ELECTRICAL DEVICES AND DISCONNECTED 
OR PROTECTED. CABLES SHALL NOT BE EXPOSED.

Summary of Contents for XAP Series

Page 1: ...xpansion Joint Installation End Cover Installation Settlement Joint Installation Horizontal Mounting Vertical Mounting Wall Penetrations Busduct Joint Clearances Tap off Unit Installation Attentions f...

Page 2: ...tored in a covered clean dry space which is climate controlled to prevent condensation Do not allow the busduct to come in contact with corrosive fumes liquids salts or forms of concrete Storing the b...

Page 3: ...ion When connecting pieces of the Eaton XAP busduct together make certain that contact surfaces are clean and free from contaminants Some section may have electrical lubricant on the contact surfaces...

Page 4: ...the installation drawing Notes after completion of one line installation it is necessary to loosen all M6 25 bolts in the expansion joints to ensure expansion effect see Figure 7 Figure 7 Expansion J...

Page 5: ...dened at the joints 3 Care should be given when locating drop rods in order to avoid placing hangers at joint and tap off unit locations Adequate ceiling clearance must be allowed for tap off units Ve...

Page 6: ...able to avoid movement 2 Tap off unit shall not be burdened with load directly Loads at the rear end shall be fastened onto the busduct or other fixed positions in accordance with regulations 3 When n...

Page 7: ...st be kept clean during installation 2 Busducts must be adjusted and kept in the same line before fastening the bolts of joint units Tolerance of assembly in horizon and vertical direction are 5mm per...

Page 8: ...the mechanisms of all electrical and mechanical interlocks and padlocking means 8 Check for missing or broken parts rusting corrosion dirt and excessive wear 9 Check the line and load connections to e...

Page 9: ...the environment through the use of power management technologies and services Eaton has approximately 95 000 employees and sells products to customers in more than 175 countries For more information...

Reviews: