background image

 

 

 

 

I.L. 5229B79H05

 

 

Effective 06/2014

 

 

Instructions for the Type VCP-W 27 kV Simple Manual Ground and 
Test Device 

 

 

 

Figure 1 Type VCP-W 27 kV Manual Ground & Test 
Device 
 
 
 
 

TABLE OF CONTENTS 

 

1-1  Introduction  ..................................................... 1 
1-2  Description  ...................................................... 1 
1-3  Operation  ........................................................ 2 
1-3.1 Safe Practices  ................................................. 2

 

 
 
 
Available Style Numbers & Options 
 

STYLE NUMBER     DESCRIPTION 

1C94354G01………..1200/2000A Top & Bottom 
1C94354G11………..1200/2000A Top & Bottom 
                                      with Direct Roll-On-Floor 
                                      (ROF) wheels installed* 
 
*Roll-On-Floor option requires breaker cell to be 
a Direct-Roll-In cell. 

 
 
 
 
 
   

 

 

WARNING

 

READ AND UNDERSTAND THESE INSTRUCTIONS 
BEFORE ATTEMPTING TO USE THIS DEVICE. 
IMPROPER USE CAN RESULT IN DEATH, BODILY 
INJURY AND/OR PROPERTY DAMAGE. 

 

 

CAUTION

 

BECAUSE OF THE UNIQUE APPLICATION AND 
VAST VARIETY OF SYSTEM AND USER 
REQUIREMENTS, SPECIFIC OPERATING 
PROCEDURES MUST BE DEVELOPED BY THE 
USER. FAILURE TO DEVELOP THESE 
PROCEDURES COULD LEAD TO IMPROPER USE 
OR OTHER MORE SERIOUS CON-SEQUENCES. 

1-1 INTRODUCTION 

Type VacClad-W switchgear assemblies are 
designed with all the bus work completely insulated 
for safety. Since the current carrying parts are not 
readily accessible, the Type VCP-W Simple Manual 
Ground and Test Device is designed for insertion into 
the breaker compartment to gain access to the 
primary stationary contacts. It provides a convenient 
means to: 
 

1. 

Ground a circuit for maintenance work; 

2. 

Apply potential for cable testing; and, 

3. 

Access both bus and line circuits for 

“phasing 

 

out” tests. 

 

1-2 DESCRIPTION 

 
The device consists of a drawout element that can be 
inserted into a circuit breaker compartment in the 
same manner as a Type VCP-W Circuit Breaker. It 
includes six terminals and ground bus connections. 
Each terminal is isolated from each other and the bus 
connection by insulating barriers. The upper and lower 
terminals are accessible by removing the respective 
front panel. The ground connection is located in the 
lower front section of the device. 
 
VacClad-W switchgear is a two-high arrangement. In 
the lower compartment the top terminals normally 
connect to the main bus and the bottom terminals 
normally connect to the incoming line or feeders.  In 
an upper

 

Reviews: