TriSync Three-Phase Vacuum Capacitor Switch

InstallatIon and operatIon InstructIons

   MN230011EN   January 2023

Ratings and specifications

Check switch ratings before installation

The TriSync capacitor switch must be applied within its 

specified ratings. Check data plate ratings and compare with 

the system characteristics at the point of application prior to 

installation. Table 1 list the ratings and specifications for the 

TriSync capacitor switch.

Ratings

All ratings meet or exceed values in IEEE Std C37.66™ 

standard for a distribution-class switch, where applicable.

Table 1 . Ratings and specifications

Voltage Class

15 kV

25 kV 

38 kV

Switch Type

110 BIL

150 BIL

200 BIL

Rated Maximum Voltage, 50/60 Hz

Ungrounded capacitor banks, L-L (kV)

15.6

25

38

Solidly grounded capacitor banks, L-L (kV)

27

38

66

Impulse Withstand Voltage

Open contact kV (BIL)

95

125

200

Line to ground (kV BIL)

110

150

200

Withstand Voltage, 50/60 Hz

Power Frequency Dry Withstand (kV)

50

70

70

Power Frequency Wet Withstand (kV)

45

60

60

Continuous current 50/60 Hz (A)

200,400

200

400

Capacitive switching current 50/60 Hz (A)

200,400

200

400

Fault making peak current (A)

15,000

15,000

32,500

Symmetrical fault making current (A)

6,000

6,000

12,500

Withstand peak current (A)

15,000

15,000

32,500

Short-time symmetrical withstand current (A)

4,500

4,500

6,250

High frequency transient making peak current (A)

9,000/12,000*

9,000

10,000

Rated transient inrush frequency (Hz)

6,000

6,000

6,000

Creepage Distance

Terminal to terminal (mm)

600

813

1,628

Terminal to ground (mm)

610

813

1,696

Operating Voltage Range, 50/60 Hz**

110/120 Vac (V)

75-130

75-130

95-130

240 Vac (V)

150-260

150-260

N/A

Nominal Control Current

110/120 Vac 

27

27

36 open, 24 close

240 Vac 

18

18

N/A

Open and close cycle time (msec)

100/100

100/100

125/100

Assembly weight, excluding control box (lb/kg)

225/102

225/102

475/215

Operating temperature range

–40 °C to +60 °C

–40 °C to +60 °C

–40 °C to +55 °C, –50 °C consult product line 

Mechanical operations

50,000

50,000

50,000

Aux. Contact Rating

110/120 Vac (A)

15

15

15

240 Vac (A)

15

15

N/A

110/120 Vdc (A)

0.20

0.20

0.20

* The 15.6 kV rated TriSync capacitor switch is available with an optional high frequency transient making peak current of 12 kA. Contact factory for additional information. 

 

 

** Contact factory for more information regarding dc control voltages. 

 

 

Note: The durability of the TriSync capacitor switch was demonstrated by completing a minimum of 50,000 mechanical operations after performing the 

 

 

Mechanical Life Test in accordance with IEEE Std C37.66™ standard. One operation is defined as 1 close and 1 open operation. 

 

 

Summary of Contents for TriSync COOPER POWER MN230011EN

Page 1: ...TriSync Three Phase Vacuum Capacitor Switch Installation and Operation Instructions COOPER POWER SERIES Vacuum Switches MN230011EN Effective January 2023 New issue...

Page 2: ...ICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUME...

Page 3: ...initial inspection 1 Handling and storage 1 Standards 1 Quality standards 1 Description of operation 1 RATINGS AND SPECIFICATIONS 2 Check switch ratings before installation 2 Ratings 2 INSTALLATION PR...

Page 4: ...us situation which if not avoided will result in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indica...

Page 5: ...epresentative Acceptance and initial inspection Each capacitor switch is completely assembled inspected tested and adjusted at the factory It is in good condition when accepted by the carrier for ship...

Page 6: ...t A 6 000 6 000 12 500 Withstand peak current A 15 000 15 000 32 500 Short time symmetrical withstand current A 4 500 4 500 6 250 High frequency transient making peak current A 9 000 12 000 9 000 10 0...

Page 7: ...quipment Failure to comply can result in death severe personal injury and equipment damage T223 2 WARNING This equipment is not intended to protect human life Follow all locally approved procedures an...

Page 8: ...s are shown in Figure 3 Accessories are shown with dashed lines These diagrams apply only for alternating current ac control voltage For direct current dc control voltage please contact your Eaton s C...

Page 9: ...Switch Coil Interrupting Switch Indirect Auxiliary Switch Direct Auxiliary Switch Direct Auxiliary Switch D 6 Pin Three Wire Control with Form C Auxillary Switch Accessory H 10 Pin Three Wire Control...

Page 10: ...to follow proper safety practices can result in contact with high voltage which will cause death or severe personal injury G112 1 The TriSync switch features a manual gang open operation operating all...

Page 11: ...X XXX 01 X 1 TITLE DESC DWG DATE REF SHEET PGR 11 4 2021 SCALE OF 2 5 THIS DRAWING HAS BEEN GENERATED FROM A 3D MODEL ECS 3 Phase Frame 25kV ECS 25 kv 3 Phase Switch and Frame assembly 150 BIL 3 Phase...

Page 12: ...enance however the switch should be inspected on a regular basis to check for physical damage and to verify operation Frequency of inspection Because these switches are applied under widely varying op...

Reviews: