Operation through
MODBUS RTU
52
07/09 MN03407002Z-EN
Checking the SmartWire configuration
The SmartWire connection system initializes when the
configuration key on the MODBUS RTU gateway is pressed.
During this process, addresses are automatically assigned to
all stations and their device files are read in to the MODBUS
RTU gateway. A correct system initialization can be verified
through register areas 40079 to 40142 (manufacturer and
device ID) and register 40143 (number of SmartWire
stations). Within the manufacturer and device ID register
area all stations are listed with the device data that the
gateway read during initialization. The number of SmartWire
stations that the gateway recognized during its initialization
is contained in register 40143. Incorrectly initialized
SmartWire stations are not included in the register areas for
manufacturer and device ID and for the number of
SmartWire stations.
Before operation, read out both register areas and compare
them with the physical layout of the SmartWire rung. This
will help you identify any faulty modules of communication
connections before starting operation.