Terminating resistors
19
07/09 MN03407002Z-EN
Terminating resistors
If the RS485 communication standard is used, the first and
last station in a MODBUS RTU field bus segment must
terminate the field bus with an energized termination
resistor. The bus termination resistor is connected externally,
either as a separate terminating resistor or through a special
D-sub connector with built-in bus termination. Connect the
terminating resistor, which should have a resistance of
150
(0.5 W) between the two signal lines RxD/TX (A-line)
and Rx/Tx+ (B-line).
EMC-conformant wiring of
the network
Electromagnetic interference can cause faults in the field
bus. Their influence can be limited by implementing suitable
EMC measures, such as:
• EMC-conformant system configuration
• EMC compliant cable installation and
• Avoiding high potential differences
• correct installation of the MODBUS systems (cables,
bus plug connection, etc.)
The electromagnetic interference can be significantly
reduced by the use of a cable screen (shield). The following
illustrations indicate the correct method for connecting the
shield.