Sonix Hmi-Tu Technical Manual

SONIX HMI-TU TECHNICAL MANUAL  

TM377 / A  June 2022  www.eaton.com

8   Appendix A – Hmi-Br - Safety  

Interface Board

A.1.  Introduction

The Hmi-Br is a safety interface intended to be installed 

in the non-hazardous area to provide an intrinsically safe, 

Zener clamped, resistively limited output to the Eaton 

MEDC Hmi-5 access panel which is installed within the 

hazardous area.

A.2.  Installation

The Hmi-Br safety interface comprises a single PCB 

mounted to a DIN rail non-metallic holder. The PCB is 

fully encapsulated within the holder to form a tamper 

proof unit. Two user terminals are provided at either end 

of the unit to allow for connection of intrinsically safe 

(marked Hazardous) and non-intrinsically safe (marked 

Non-Hazardous) wiring. In addition to these terminals 

the unit is also provided with a threaded metallic earth 

stud to allow for the connection of the I.S. safety 

earthing.

The Hmi-Br safety interface board should be mounted 

in the non-hazardous area, within an enclosure which 

provides suitable ingress protection and a minimum 

protection of IP20.

The product must not be installed in an environment 

where it may be attacked by aggressive substances.

Cable termination should be performed by suitably 

trained personnel in accordance with IEC EN 60079-14.

The non-intrinsically safe terminals are rated for a Um of 

250V

The HMI-BR is a four-channel device that provides the 

following entity parameters per connection point. All 

connection points are with respect to the local I.S. Earth.

Aud1

Aud2

Dat1

Dat2

Uo

26.1 V

26.1 V

7.9 V

7.9 V

Io

137.4 mA

137.4 mA

36.3 mA

36.3 mA

Po

897 mW

897 mW

72 mW

72 mW

Ci

0µF

0µF

0µF

0µF

Li

0µH

0µH

0µH

0µH

ote: 

N

Aud1 / Aud2 have a minimum series resistance of 190Ω and  

Dat1 / Dat2 have a minimum series resistance of 217Ω.

A.3.  Maintenance

This equipment should require little or no maintenance 

during its working life. However, if abnormal or unusual 

environmental conditions occur due to mechanical 

damage or accidents then visual inspection is 

recommended 

The Hmi-Br contains no user replaceable parts and shall 

not be repaired by the user. Contact Eaton MEDC Ltd for 

replacement if required.

A.4.  Certification

ATEX

ATEX certificate number: ITS 13ATEX27896X

Certified to EN 60079-0, EN60079-11, EN60079-26

 

II (1) G [Ex ia Ga] IIC

 T

amb

: -40ºC to +60ºC

IECEx

IECEx certificate Number: IECEx ITS 13.0047X 

Certified to IEC 60079-0, IEC 60079-11, IEC 60079-26

 

[Ex ia Ga] IIC

 

-40°C ≤ Ta ≤ 60°C

Special Conditions For Safe Use

• 

The apparatus is only permitted to be used with 

products manufactured by Eaton MEDC Ltd, or its 

derivative companies. In addition to this, the suitability 

of apparatus to interact with any external equipment 

shall be evaluated and stated explicitly on the 

equipment certification.

• 

The apparatus must be installed within an enclosure 

providing a suitable degree of protection as to prevent 

ingress of conductive materials with a minimum rating 

of IP20.

• 

The ambient local to the apparatus in its final 

installation shall not exceed the specified ambient 

temperature range -40ºC ≤ Ta ≤ +60ºC.

• 

Isolation between the intrinsically safe interface 

and the external enclosure is to be verified upon 

installation by the application of a dielectric strength 

test. The test shall be conducted as follows:

• 

A 500 V dielectric strength test is to be 

conducted upon assembly between all 

intrinsically safe circuits and the external 

enclosure. Test duration is to be a minimum of 

1 minute with an applied voltage of 500 V AC 

rms at a frequency of 48 – 60 Hz or alternatively 

a voltage of 700 V DC may be applied. Leakage 

current is not to exceed 5 mA.

Summary of Contents for SONIX Hmi-Tu

Page 1: ...SONIXTM Hmi Tu Access Panel Interface Unit SonixTM Hmi Tu Technical Manual...

Page 2: ...INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLI...

Page 3: ...to the loudspeaker and generates feedback 2Mx Sonix 2Mx Central controller Amp 350 d Sonix 350 W Power Amplifier with 100 V line output Eol1 Sonix Remote End of Line unit Eol8 Sonix Amplifier to 100 V...

Page 4: ...RJ45 bus ports 9 2 2 3 Access Panel Data and Audio connections 9 2 2 4 Local Mute Local Attenuate unit 11 2 2 5 Earth Stud 11 3 UNIT OPERATION 12 3 1 Data and audio communications 12 3 1 1 Data Commu...

Page 5: ...URE 10 MUTE CONNECTIONS 11 FIGURE 11 HMI FILTER CONNECTION DETAILS 12 FIGURE 12 DUAL BUS CONNECTIONS 13 FIGURE 13 CASCADED UNITS 13 FIGURE 14 ACCESS PANEL AUDIO FAULT 14 FIGURE 15 MISSING ACCESS PANEL...

Page 6: ...products we provide adequate packaging to protect the goods during transit Please ensure that once unpacked checked and installed that all packaging is disposed of or recycled in a responsible manner...

Page 7: ...ised if required please contact your local Eaton representative to discuss requirements The unit provides 4 ports that can be configured for either Hmi 26 or Hmi 5 connections Each port also provides...

Page 8: ...annel 2 Hmi 26 Hmi 5 configuration links 9 Channel 3 Hmi 26 Hmi 5 configuration links 10 Channel 4 Hmi 26 Hmi 5 configuration links 11 Earthing stud 12 Channel 1 mute control output J2 13 Channel 2 mu...

Page 9: ...power management unit A green LED alongside the connector indicates the unit is powered ote N As these cables are power feeds they should be routed within the PA GA system in a way to avoid contact w...

Page 10: ...positions Port ID Assignment Position 1 LK1 LK2 LK3 LK5 All in position b 2 LK4 LK6 LK7 LK8 All in position b 3 LK9 LK10 LK11 LK12 All in position b 4 LK13 LK14 LK15 LK16 All in position b Table 7 Hm...

Page 11: ...7 9 V dc 36 3 mA Screen 0V J1 2 5 Table 10 Hmi Br connection details 2 2 3 4 Access panel 0V reference The interconnecting cable screen provides the 0V return between the access panels to the Hmi Tu p...

Page 12: ...Hmi 26 protocol uses a half duplex RS485 38 400 8 N 1 connection while the Hmi 5 protocol operates at 9 600 8 N 1 on separate Tx and Rx connections 3 1 2 Hmi bus Depending on the system design and the...

Page 13: ...H1 Flt Mute Att L Spk CH2 Mute Flt 2Mx Bottom Hmi Bottom Hmi Top 2Mx Top J1 Sonix Hmi Unit 1 L Spk CH1 Flt Mute Att L Spk CH2 Mute Flt Figure 13 Cascaded units Amp Bus HMi Bus HMi Bus I O Bus COMPLIAN...

Page 14: ...pk CH2 Mute Flt Default Config Power Dist Beacon Amplifier HMI Matrix I O LOCALSTATUS Default Config Power Dist Beacon Amplifier HMI Matrix I O LOCALSTATUS Sonix 2Mx Unit Figure 15 Missing access pane...

Page 15: ...Hmi Br fuses likely blow Replace unit Check for output voltage on the Hmi Br J2 pin 3 to pin 5 approx 5 5 6 5 V J2 pin 4 to pin 5 approx 3 0 4 0 V Internal Hmi Br fuses likely blow Replace unit Check...

Page 16: ...0 H 0 H 0 H ote N Aud1 Aud2 have a minimum series resistance of 190 and Dat1 Dat2 have a minimum series resistance of 217 A 3 Maintenance This equipment should require little or no maintenance during...

Page 17: ...1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 17 Sonix Hmi Tu Technical Manual SONIX HMI TU TECHNICAL MANUAL TM377 A June 2022 www eaton com THIS PAGE IS INTENTIONALLY LEFT BLANK...

Page 18: ...aton and SONIX are registered trademarks All other trademarks are property of their respective owners Changes to the products to the information contained in this document and to prices are reserved s...

Reviews: