System Options Menu
Page 57
Note:
If you are using Fast Format communications, please ensure that one channel is
allocated for tamper. If you do not do this, the control unit reports tamper as an
unconfirmed Burg to ensure the condition is notified.
Abort Time
Use this option to change Alarm Abort Delay period. The timer can take any value in the
range 0 to 120 seconds.
The control unit starts the Alarm Abort Delay timer whenever it starts an alarm. If a user
silences an alarm within the Abort Delay period, the alarm will not require an installer or
remote reset.
If an alarm occurs and a user unsets the system
within
the Alarm Abort Delay period, the
control unit activates any output of type Alarm Abort (page 38) and starts any Alarm Abort
Fast Format communications programmed.
Auto Rearm
This option is available when
Confirmation Mode
is set to Basic.
Use this option to specify the number of times that the system will re-arm when the siren
time expires.
Select NEVER to make the system never re-arm (the system will go into alarm once only).
Select one of the other options to make the system re-arm once, twice, three, four or five
times, or always. The system re-arms all closed zones, but not detectors that are still
sending alarm signals. (Note that this setting is required in order to comply with EN50131
.
)
If the system has rearmed, then when a user enters the system through the Final Exit
door, the control unit will give an audible internal alarm in place of the normal entry tone.
Hardware
Panel Name
You can use this option to give the control unit a name. The name is displayed only when
using the
About, Panel
option (page 65).
Wired Zone Type
The control unit prompts you to select the zone wiring type when you power up a control
unit for the first time, or when you restore the control unit to factory defaults (see page 51).
Panel Zones
This option lets you change the zone wiring type for the control unit.
Please refer to page 14 for details of the wiring types.
Panel Loudspeaker
Volume
Use this option to change the volume of chime, entry, exit, alert, confirmation and
other tones from a loudspeaker connected to the control unit. This volume control
does NOT change the volume of alarm tones. You can separately adjust the volume
of each type of tone.