System Operation
Copyright © 2007-2018 Eaton Corporation. All Rights Reserved.
IPN 997-00012-03 B2 Issue B2 July 2018
31
Configuration
Set the following parameters.
Parameter
Description
Where to find:
First Start Time
The date and time that the first battery test cycle will
occur. Subsequent tests will occur at every Battery Test
Interval after that.
SC300: Control Processes >
Battery Test
DCTools/Web: Control
Processes > Battery Test
Interval
The time between scheduled battery tests. The interval
period begins at the start of a battery test. Zero disables
scheduled battery tests. Zero also disables the 48 hour
lockout following an ac supply failure, allowing an
immediate manual test.
Test Duration
The maximum time a Battery Test process will be
active. The battery test will pass if the bus voltage
remains above the Battery Test Termination Voltage
for the duration of the test.
Termination
Voltage
If the bus voltage drops below this value during a
Battery Test, then the test fails.
Prevent Battery
Test
Choose whether the alarm Battery Fuse Fail should
prevent Battery Test starting.
Equalize
Equalize charges batteries at a higher voltage after they have been fully charged to ensure that all
individual cell voltages are the same, that electrolyte is distributed evenly, and that sulfate crystal
buildup on the plates is reduced.
Equalize can be scheduled to occur at regular intervals and/or can be started/stopped manually.
Refer to the battery manufacturer's instructions before using Equalize.
If a Digital Input has the function "Start Equalize" then a manual equalize cycle will start when
the Digital Input becomes active.
If Equalize cannot start at the scheduled time (for example when there is no ac supply) then its state
will be Pending and it will start as soon as conditions allow. Use Stop Equalize to cancel a Pending
Equalize.
► To enable Equalize (or to start or stop Equalize manually)
•
Use the SC300 keypad to go to:
Control Processes > Equalize
.
•
Or, in DCTools/Web go to:
Control Processes >
Equalize
.
► To use an external relay contact to activate an Equalize (optional)
•
Connect a voltage free relay contact or switch to any Digital Input.
•
In DCTools/Web go to:
Digital Inputs
.
•
Configure the selected Digital Input and set
Function
to
Start Equalize
.
► To use a Smart Alarm to activate an Equalize (optional)
•
Configure a Smart Alarm as required to activate Equalize.
•
Set
Activating Smart Alarm
to the Smart Alarm Number.