Active Alarm Indications
All alarms have a configured
Severity:
Critical Major Minor Warning Control
The
Severity
determines how an active alarm is indicated:
Severity
Alarm indications
Details
SC200 Major alarm LED will turn on.
See details on page
SC200 Minor alarm LED will turn on.
See details on page
If the SC200 audible indicator is enabled, it will
sound until a key is pressed.
See details on page
The alarm name and severity icon will be
displayed on the SC200 main screen.
See details on page
The
Event Log
will record the alarm activation.
See details on page
If configured, an Email message will be sent to one
or more Email addresses.
See details on page
If configured, an SMS text message will be sent to
one or more cell phones.
See details on page
If configured, PowerManagerII control and
monitoring software will be notified by modem
callback. PowerManagerII can initiate various
actions when it receives an alarm notification.
Refer to the
PowerManagerII online
Help.
In DCTools/Web (if connected), the alarm name
and severity icon will be displayed in the
Alarms
list on the
System
page.
See DCTools screen on
page
, Web screen on
If configured, an SNMP Trap will be sent to a
network management system (NMS).
See details on page
If configured, a note will be displayed on the
SC200 and included in the SNMP trap (if used).
Refer to the alarm's
configuration details.
If configured, one or two digital outputs (relays)
will be operated.
Refer to the alarm's
configuration details.
► To view a list of active alarms
Use the SC200 keypad to go to:
Alarms
.
Or, in DCTools/Web go to
System
.