Enterprise Power Solutions Installation and Operation Guide
32
Copyright © 2008 Eaton Corporation. All Rights Reserved.
IPN 997-00012-56C September 2008
2
After start-up of the system controller:
•
Press any key on the system controller to silence the alarm (SC200 only).
Depending on the configuration file settings, one or both alarm LED(s) may be on and the
system controller may display some system alarm messages. This is normal. For an
explanation of alarm messages see Alarm Descriptions in the System Controller Operation
Handbook.
•
The LCD display module shows the summary screen. See details on page
.
If no load or battery is connected the current will be 0A.
•
If fitted and enabled, the LVD(s) operate.
3
Check all rectifiers are running and only the rectifier green Power On LEDs are on (no
alarm LEDs).
•
On the system controller keypad select
Menu
>
Rectifiers.
See details on page
.
Check that all rectifiers are registered.
If any problems see Troubleshooting on page
After start-up of the system controller there will be a loud click when the battery disconnect
LVD operates. This is normal operation.
Task 4 - Configuring the DC Power System
The operational settings of the dc power system are stored in a configuration file loaded into
the SC200 or SC100 system controller. See details in the System Controller Operation
Handbook (see Related Information) on page
.
Make the following configuration changes, if required:
Step 1 - Systems with batteries connected
Ignore this Step if the EPS2/EPS5 system does not have batteries connected.
•
In the SC200 or SC100 configuration file, set the battery capacity according
to the number of battery modules connected:
•
Either:
On SC100 go to:
Menu > Configuration > System > Edit > Battery
Capacity >Edit
, or
On SC200 go to:
Battery > Battery > Battery Capacity
.
•
Set
Battery Capacity
to the number of battery modules x 18Ah.
•
Go to Step 3.