Eaton RSPF Series Installation Instructions Manual Download Page 3

 

RSPF Series Surge Protective Device 

IL158004EN

 

Rev. 2 – December 2017 

 

Page 1 

1  Introduction 

1.1 

Manual Introduction 

This installation manual describes the installation and 
operation of the Eaton RSPF Series Surge Protective 
Device (SPD).  This technical document covers most 
aspects of installation and operation. This document is a 
guide only for licensed/qualified electricians. If you 
require further information regarding a particular 
installation, application, or maintenance activity, please 
contact your Eaton representative. These instructions do 
not cover all details, variations or combinations of the 
equipment, its storage, delivery, installation, check-out, 
safe operation or maintenance. Care must be exercised 
to comply with local, state, and national regulations, as 
well as safety practices for this class of equipment. 

Please read and understand ALL installation and 
operating instructions prior to installation and use of 
this equipment.

 

1.2 

Product Overview 

The Eaton RSPF Series SPD protects critical electrical 
and electronic equipment from damage by voltage 
transients and surges when properly installed. This is 
done by shunting high energy lightning surges (and 
other transient disturbances) away from the equipment 
being protected. It does this in nanoseconds by 
providing a low impedance surge path to ground through 
thermally protected metal oxide varistors while 
supporting power frequency voltage.  Proper installation 
is critical to ensure the SPD operates as intended. 

The Eaton RSPF Series SPD was designed and 
developed to fit in the space of an Eaton FD-Frame 
molded case circuit breaker for retrofit into existing 
panelboards or switchboards with space or provisions for 
an additional FD-Frame molded case circuit breaker. 

This device features internal protection that will 
disconnect the surge protective component under fault 
conditions but will maintain power to the load, now  
unprotected from surge events. 

The Eaton RSPF Series SPD is available in voltage 
ratings from 208Vac to 600Vac and surge current ratings 
of 50kA and 100kA.  The enclosure measures 6.00” x 
4.125” x 3.807” (152.40mm x 104.775mm x 96.6978mm) 
with a maximum weight of ~3 lbs (~1.36 kg). 

The Eaton RSPF Series is available in nine options, see 

Section 10, Ordering Guidelines 

for more details 

 

 

 

1.3 

Safety Precautions 

  WARNING   

WARNING – SHOCK HAZARD – DO NOT OPEN.  
AVERTISSEMENT: RISQUE DE DECHARGE 
ELECTRIQUE – NE PAS OUVRIR. 

WARNING NO SERVICEABLE PARTS.  ATTENTION : 
AUCUNE PIÈCE REMPLACABLE OU RÉPARABLE. 

A LICENSED/QUALIFIED ELECTRICIAN MUST 
COMPLETE ALL INSTRUCTIONS IN THIS MANUAL 
IN ACCORDANCE WITH THE NATIONAL ELECTRIC 
CODE (NEC), CANADIAN ELECTRICAL CODE (CEC), 
STATE, AND LOCAL CODES, OR OTHER 
APPLICABLE COUNTRY CODES.  ALL APPLICABLE 
LOCAL ELECTRICAL CODES SUPERSEDE THESE 
INSTRUCTIONS. 

CHECK THE VOLTAGE-RATING LABEL LOCATED 
ON THE FRONT OF THE SPD TO VERIFY THAT THE 
ELECTRICAL SYSTEM’S VOLTAGE  ARE THE SAME 
AS THE SPD. 

CONDUCTING DIELECTRIC, MEGGAR, OR HI-
POTENTIAL TESTING WITH THE SPD INSTALLED 
WILL CAUSE INTERNAL DAMAGE TO THE SPD.  
THE SPD WILL CAUSE THE TEST TO FAIL. 

IMPROPER INSTALLATION COULD CAUSE DEATH, 
INJURY AND EQUIPMENT DAMAGE.  FOLLOW ALL 
WARNINGS AND CAUTIONS.  COMPLETELY READ 
AND UNDERSTAND THE INFORMATION IN THIS 
INSTRUCTION MANUAL BEFORE ATTEMPTING TO 
INSTALL OR OPERATE THIS EQUIPMENT. 

ARC FLASH DURING INSTALLATION COULD 
CAUSE INJURY OR DEATH.  USE APPROPRIATE 
SAFETY PRECAUTIONS AND EQUIPMENT FOR ARC 
FLASH PROTECTION. 

INSTALLING A PROTECTION DEVICE WHICH IS 
UNDER RATED FOR THE ELECTRICAL SYSTEM 
VOLTAGE CAN CREATE A POTENTIALLY 
HAZARDOUS CONDITION. 

CHECK THE FACILITY’S GROUNDING SYSTEM. ALL 
GROUNDING, BONDING AND EARTHING 
PRACTICES MUST MEET NEC, CEC AND LOCAL 
APPROVED PRACTICES. A POOR GROUND, OR A 
GROUNDING / BONDING VIOLATION WILL 
SERIOUSLY AFFECT THE SPD’S ABILITY TO 
FUNCTION AS SPECIFIED. 

ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT 
BEFORE PROCEEDING WITH THE TASK AND 
ALWAYS FOLLOW ALL SAFETY PROCEDURES. 

 

 

Summary of Contents for RSPF Series

Page 1: ...ffective Date December 2017 For more information visit www eaton com RSPF Installation Instructions for Eaton RSPF Series Surge Protective Device SPD Instruction Leaflet IL158004EN Rev 2 December 2017...

Page 2: ...ted to the Ground Bus 5 Figure 9 Surge Ground Terminal connected to the Neutral Bus 5 5 Operation 5 5 1 Power Up and System Checkout 5 5 2 Alarm Silence Pushbutton 5 6 Specifications 6 7 Maintenance 6...

Page 3: ...nditions but will maintain power to the load now unprotected from surge events The Eaton RSPF Series SPD is available in voltage ratings from 208Vac to 600Vac and surge current ratings of 50kA and 100...

Page 4: ...NTRY CODES ALL APPLICABLE LOCAL ELECTRICAL CODES SUPERSEDE THESE INSTRUCTIONS INSTALLING AN SPD THAT IS IMPROPERLY RATED FOR THE ELECTRICAL SYSTEM VOLTAGE COULD CREATE A POTENTIALLY HAZARDOUS CONDITIO...

Page 5: ...AUSE INJURY OR DEATH USE APPROPRIATE SAFETY PRECAUTIONS AND EQUIPMENT FOR ARC FLASH PROTECTION 4 3 Mounting 1 Locate the electrical system s applicable block diagram in Section 5 Wiring Diagrams 2 Tur...

Page 6: ...tripe 10 AWG insulated conductor Keeping the wire length as short as possible Torque the Surge Ground Terminal screw to 35 lb in See Figure 6 11 2 When wiring to the Neutral Bar use a white 10 AWG ins...

Page 7: ...nnections and test again Verify that the proper voltage is present If the panel is energized properly and the LEDs still do not light contact EatonCare Technical Resource Center at 1 800 809 2772 Opti...

Page 8: ...under warranty 8 Liability This instruction leaflet is published solely for information purposes and should not be considered all inclusive If further information is required you should consult Eaton...

Page 9: ...ailable at www eaton com Current Eaton Panelboards Renewal Parts RP01400001E Eaton Renewal Parts Data Panelboard Renewal Parts Supplement RP01414001E Vintage Cutler Hammer panelboards and switchboards...

Page 10: ...stitute any warranty by or impose any liability upon Eaton AND IS IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESSED IMPLIED OR STATUTORY AS TO THE MERCHANTABILITY FITNESS FOR PURPOSE SOLD PRODUCTIVE N...

Page 11: ......

Page 12: ...ownship PA 15108 4312 USA www eaton com RSP 2017 Eaton Corporation For additional information please call All Rights Reserved Eaton s Power Quality Technical Support Publication No IL158004EN 1 800 80...

Reviews: