164
Eaton RF-System - Help
© 2015 Eaton Electrical Group
Please make sure that every ECI in the project has a unique IP-address or it will not work
correctly.
Also see
Multi-Heating actuator
The Multi-Heating actuator is a mains supplied device that can be used to control electrical valves
for Panel heating- and cooling-systems (Floor heating,…). Up to 12 different zones and a
maximum of 14 vales can be controlled by the device.
It has 12 inputs for Set- and Actual temperature, a sum output, an error output, a binary input for a
dew point sensor and an input for Heating/Cooling toggle.
The temperature information for the each of the 12 inputs can either be sent by a Room-controller
(Type CRCA-00/06 or CRCA-00/07), a Room-Manager, a Home-Manager or other intelligent
devices like Ethernet CI, USB-RF-Communication-Stick etc.
In the configuration window of the Multi-Heating actuator (right click on the device symbol and
selection of „configuration“) you can find information about the connected devices for each channel
and the Software- and Hardware-Version of the device.
Detailed information about the connection of the electrical valves and the different wiring
possibilities can be found in the mounting instruction.
General information about the different channels of the Multi-Heating actuator:
Heating inputs 1-12
Inputs for Set- and Actual-temperature from Room-controllers, Room-Manager
etc.
Sum output:
Output that can be connected to any actuator (for controlling a pump etc.). Its
state depends on the state of each of the 12 valve outputs.
Error output:
Output that can be connected to any actuator. It will be ON if any error occurs
(no temperature information, low battery of connected sensors etc.)
Input: dew
sensor
Input for a binary dew point sensor. If it receives an ON message cooling is not
allowed.
Input:
Heating/Coolin
g toggle
Input for the toggle of the operation type between Heating and Cooling
(OFF=Heating, ON=Cooling)
Operation with Room-Controller:
In this case one or more Room-controller (Type CRCA-00/06 or CRCA-00/07) are used to provide
the Room- and Set-temperature. Each Room-controller can be connected to multiple inputs of the
Multi-Heating actuator but each input can only have one connection. The Room-controller needs to
be set to the Mode „Send temperature value“.
The values of the Set-temperatures for Comfort and Eco mode can be set in the configuration
window of the Room-controller. Using the Mode-switch on the Room-controller you can toggle
between comfort and Eco mode. Additionally the set value can also be changed by the customer
b3°C and -3°C using the control wheel.
Summary of Contents for RF System 2.42
Page 1: ...Eaton RF System 2 42 Manual...
Page 123: ...123 Eaton RF System 2015 Eaton Electrical Group State Syntax of RM to user...
Page 193: ...193 Eaton RF System 2015 Eaton Electrical Group...
Page 200: ...200 Eaton RF System Help 2015 Eaton Electrical Group 7 And assign the function Blinking to it...
Page 223: ...223 Eaton RF System 2015 Eaton Electrical Group Group settings analogue actuator...
Page 224: ...224 Eaton RF System Help 2015 Eaton Electrical Group Group settings heating actuator...
Page 225: ...225 Eaton RF System 2015 Eaton Electrical Group Group settings binary input battery supplied...
Page 227: ...227 Eaton RF System 2015 Eaton Electrical Group Group settings Temperature input...