2.6 Power bus
The power bus supplies RAMO5 and RASP5 Rapid Link modules with
power. Plug-in outgoers can be quickly and safely connected at any point
along the bus. The power bus can consist either of a flexible busbar (ribbon
cable) or standard round cables.
Figure 17: Sample configuration of a Rapid Link system with RAMO5 and RASP5 units
Observe the following when planning the lengths of the power bus cabling:
•
In the event of a single-pole short circuit at the end of the energy bus,
e. g. in the motor terminal board of the last user, the upstream protec-
tive device must be triggered. The level of short-circuit current depends
on:
•
Cable length,
•
Conductor cross-section,
•
Short-circuit current at the incoming point
•
The level of the application-specific voltage drop depends on:
•
Cable length,
•
Conductor cross-section,
•
Current consumption of motors
ATTENTION
•
All devices connected to the apparatus and data bus must
also meet the requirements for safe isolation according to
IEC/EN
60947-1 Annex N or IEC/EN
60950.
•
Power supply units for the AS-Interface power supply must
meet the safe isolation requirements according to SELV.
M
3 ∼
1.5 mm
2
4 mm
2
4 mm
2
3 AC 400 V∼,
50/60 Hz
Q1
M
3 ∼
M
3 ∼
1.5 mm
2
1.5 mm
2
RAMO
RASP
M
3 ∼
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
RASP
1.5 mm
2
RAMO
I >
I >
210 A
F
25 A
Summary of Contents for Rapid Link RAMO5
Page 1: ...Manual Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN ...
Page 4: ...II ...
Page 10: ...6 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 122: ...4 Operation 4 3 Manual control 118 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 158: ...8 PC tool 8 2 Parameter Editor 154 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 208: ...11 Communications 11 5 OP Bus 204 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...