1 Rapid Link system 5
1.5 UL Standards Compliance
Rapid Link 5 · RAMO5 · RASP5
10/19 MN034004EN
www.eaton.com
23
1.5.2 RASP5
RASP5 motor starters have been tested in accordance with UL 61800-5 and
are approved as “listed”.
Table 5:
RASP5
Table 6:
Short circuit current rating for individual and group protection
Property
Value
Input voltage
480 V AC
Output voltage, maximum
480 V AC
Rated operating voltage for brake
control
180 V DC
230 V AC
400 V AC
Output current
2.5 A (RASP5-2…S1)
4.3 A (RASP5-4…S1)
5.6 A (RASP5-5…S1)
8.5 A (RASP5-8…S1)
Input current
2.4 A (RASP5-2...)
4.1 A (RASP5-4...)
5.3 A (RASP5-5...)
7.8 A (RASP5-8...)
Frequency
50/60 Hz
Phases
3
Output frequency
0 - 320 Hz
Field bus input voltage
30 V DC
Motor protection
integrated,
At 105 % full load
Thermistor monitoring
integrated
Degree of protection
NEMA 12/NEMA 12K
Ambient temperature, maximum
40 °C without fan
55 °C with fan
With fuse (UL listed)
Circuit-breakers (UL listed)
with built-in
local discon-
nect switch
without built-
in local
disconnect
switch
with built-in
local discon-
nect switch
without built-
in local
disconnect
switch
Voltage
480 V AC
480 V AC
480 V AC
480 V AC
Short-circuit current,
maximum
30 A
30 A
32 A
32 A
Interrupting Rating
10 kA
65 kA
10 kA
10 kA
→
Devices with an integrated disconnect switch are approved for
use as “motor disconnects” (“lockout/tagout”).
Summary of Contents for Rapid Link RAMO5
Page 1: ...Manual Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN ...
Page 4: ...II ...
Page 10: ...6 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 122: ...4 Operation 4 3 Manual control 118 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 158: ...8 PC tool 8 2 Parameter Editor 154 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 208: ...11 Communications 11 5 OP Bus 204 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...