11 Communications
11.3 External quick stop
Rapid Link 5 · RAMO5 · RASP5
10/19 MN034004EN
www.eaton.com
197
11.3.3 RASP actuation
Table 45:
Control RASP5
•
The START signal or enable for the requested operating direction is
issued through DQ0 (FWD) or DQ1 (REV).
•
Through outputs DQ2 and DQ3 fixed frequencies FF1 to FF3
(digital setpoint value memory) are called up in binary code.
•
If DQ2 and DQ3 are not activated, the frequency set in FF0 is output.
Function
Signal to RASP
Outputs
Inputs
DQ0
DQ1
DQ2
DQ3
DI0
DI1
DI2
D13
No controller enable
0
0
Anticlockwise rotating field (REV)
0
1
Clockwise rotating field (FWD)
1
0
No controller enable
1
1
FF0 (P1-12 = 10 Hz)
0
0
FF1 (P2-01 = 30 Hz
1
0
FF2 (P2-02 = 40 Hz
0
1
FF3 (P2-03 = 50 Hz
1
1
Automatic mode
1
No automatic mode
0
Accumulative error
0
No accumulative error
1
external input I1 via M12 socket
no signal
0
Signal available
1
external input I2 via M12 socket
no signal
0
Signal available
1