6 RASP5 Speed controller
6.4 Special technical data
136
Rapid Link 5 · RAMO5 · RASP5
10/19 MN034004EN
www.eaton.com
6.4 Special technical data
The following tables show the technical data of the RASP5 Motor Control
Unit in the individual power classes with the allocated motor output.
→
The motor output allocation is based on the rated operational
current.
→
The motor output designates the respective active power
output to the drive shaft of a normal, four pole, internally or
externally ventilated three-phase asynchronous motor with
1500 min
-1
(at 50 Hz) and 1800 min
-1
(at 60 Hz).
Symbol
Unit
RASP5-2…
RASP5-4…
RASP-5…
RASP-8…
Rated operational current (I
e
)
I
e
A
2.4
4.3
5.6
8.5
Overload current for 60 s every 600 s at
40 °C
I
L
A
3.6
6.5
8.4
12.75
Overload current for 2 s every 20 s at
40 °C
I
L
A
4.8
8.6
11.2
17
Apparent power at 400 V rated opera-
tion
S
kVA
1.84
3.27
4.24
6.49
Assigned motor output at 440 V, 60 Hz
P
kW
0.75
1.5
2.2
4
P
HP
1
2
3
5
Settings range
Setting range current limitation
(P1-08)
l
2
A
0.2 - 2.4
0.4 - 4.3
0.5 - 5.6
0.8 - 8.5
Power side (primary side)
Number of phases
3
3
3
3
Rated voltage
U
LN
V
380 V - 15 % - 480 V + 10 %, 50/60 Hz
(380 - 480 V ±0 %, 45 - 66 Hz ±0 %)
Input current
I
LN
A
2.5
4.1
5.3
7.8
Braking
Braking value
I/I
e
%
≦
30
≦
30
≦
30
≦
30
Switch-on threshold for the braking tran-
sistor
U
DC
V DC
765
765
765
765
Summary of Contents for Rapid Link RAMO5
Page 1: ...Manual Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN ...
Page 4: ...II ...
Page 10: ...6 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 122: ...4 Operation 4 3 Manual control 118 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 158: ...8 PC tool 8 2 Parameter Editor 154 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Page 208: ...11 Communications 11 5 OP Bus 204 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...