9 Communication
9.2 EtherNet / IP
216
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
9.2.10 External 24 V DC control voltage
The control section of the RASP5 speed controller (M12 input 24 V) can be
supplied with an external voltage of 24 V DC via an external power supply.
Figure 124:
M12 input 24 V
Figure 125:
External 24-V DC control voltage
If the power is supplied by an external power supply unit, the control board
of the Rapid Link 5 module and the RJ45 interface will be active.
→
The external control voltage (+24 V DC) must be able to handle
a load of at least 100 mA.
The residual ripple of this external control voltage must be less
than ±5 %
Δ
U
a
/U
a
.