Specification are subject to change without notice. Copyright 2006 Eaton Power Quality Pty Ltd 

Installation Specification – Quickmov 

Tvss Doc# 510080 

Page 1 of 2 

 

Web: 

http://www.powerware.com.au

 Phone: 1300 UPS UPS

 

I

NSTALLATION 

S

PECIFICATION

 

Quickmov 

Surge Diverter SPDQM1 

(Point-of-entry, Single-mode, 30kA) 

APPLICATIONS

 

• 

Multi-storey buildings 

• 

Commercial and Industrial sites 

• 

UPS and Computer systems 

• 

Telecommunication Systems 

• 

Process Control System

FEATURES 

• 

Surge suppression rating of 30kA, 20 times 

• 

Protection fail indicator 

• 

Fits any Cutler-Hammer Quicklag™ SWB. 

• 

Includes built-in HRC fuse 

 

FUNCTIONAL DESCRIPTION 

The Q

UICKMOV

 surge diverter is designed to provide point-of-entry protection against surge transients for services 

rated at 100A or greater. The unit is intended for installation at the M.E.N. point, or to be used in conjunction with 
an SPD50NGi Neutral-Earth protector in non-M.E.N. locations (contact Eaton Powerware for details). One 
Q

UICKMOV

 per phase is required for multi-phase installations. 

 
Due to inbuilt protection mechanisms, no external fuse or circuit breaker is required. In fact, no other parts, apart 
from the Quickmov itself are required for installation - the unit simply installs like a standard Q

UICKLAG

™ 

device, 

except with the free terminal being replaced with a short length of cable. This cable is connected to the Neutral bar 
of the switchboard.  
 
The Q

UICKMOV

 has been designed in accordance with AS3100, ANSI-IEEE C62.41, IEC61643-1, IEC61000-6-1, 2, 

3, 4 and other standards and codes as applicable. 

INSTALLATION  

• 

Isolate the incoming power circuit before installation. 

• 

All wiring must be carried out by suitably qualified personnel according to the applicable standards. 

 
1.  Remove SWB panel and determine where the unit(s) shall be mounted. Units should be installed so that the 

cable length from the Quickmov to the Neutral bar is minimised. 

2. 

Install unit(s) to SWB pan and tighten the busbar terminal screw. Trim the black wire(s) to the minimum length 
required to terminate to the neutral bar, leaving no more than 50-60mm slack in the cable.  

Always use as short a length of cable as necessary. DO NOT EXTEND CABLE. If cable is too short, move other 
devices away to create a space for the Quickmov unit(s). Avoid sharp bends in cables. 
3. 

Connect trimmed cable(s) to neutral bar. 

4. 

Replace SWB panel and restore power. 

EARTHING 

For proper operation, all surge diverters rely upon a good earth connection. In some installations the existing earth 
system may require upgrading. Important things to look for are that the main earth wire (from earth link on 
switchboard to ground rod or system) should preferably be 10mm

2

 or greater and must be as short as possible.  

Failure to consider the above points can result in improper operation of the unit and possible damage to 

the installation. 

OPERATION

 

The status of the Q

UICKMOV

 is indicated by a flag visible through the window on the front face of the unit. The flag 

changes colour from green to red if the unit is damaged and requires replacement.  