Specification are subject to change without notice. Copyright 2006 Eaton Power Quality Pty Ltd
Installation Specification – Quickmov
Tvss Doc# 510080
Page 1 of 2
Web:
http://www.powerware.com.au
Phone: 1300 UPS UPS
I
NSTALLATION
S
PECIFICATION
Quickmov
Surge Diverter SPDQM1
(Point-of-entry, Single-mode, 30kA)
APPLICATIONS
•
Multi-storey buildings
•
Commercial and Industrial sites
•
UPS and Computer systems
•
Telecommunication Systems
•
Process Control System
FEATURES
•
Surge suppression rating of 30kA, 20 times
•
Protection fail indicator
•
Fits any Cutler-Hammer Quicklag™ SWB.
•
Includes built-in HRC fuse
FUNCTIONAL DESCRIPTION
The Q
UICKMOV
surge diverter is designed to provide point-of-entry protection against surge transients for services
rated at 100A or greater. The unit is intended for installation at the M.E.N. point, or to be used in conjunction with
an SPD50NGi Neutral-Earth protector in non-M.E.N. locations (contact Eaton Powerware for details). One
Q
UICKMOV
per phase is required for multi-phase installations.
Due to inbuilt protection mechanisms, no external fuse or circuit breaker is required. In fact, no other parts, apart
from the Quickmov itself are required for installation - the unit simply installs like a standard Q
UICKLAG
™
device,
except with the free terminal being replaced with a short length of cable. This cable is connected to the Neutral bar
of the switchboard.
The Q
UICKMOV
has been designed in accordance with AS3100, ANSI-IEEE C62.41, IEC61643-1, IEC61000-6-1, 2,
3, 4 and other standards and codes as applicable.
INSTALLATION
•
Isolate the incoming power circuit before installation.
•
All wiring must be carried out by suitably qualified personnel according to the applicable standards.
1. Remove SWB panel and determine where the unit(s) shall be mounted. Units should be installed so that the
cable length from the Quickmov to the Neutral bar is minimised.
2.
Install unit(s) to SWB pan and tighten the busbar terminal screw. Trim the black wire(s) to the minimum length
required to terminate to the neutral bar, leaving no more than 50-60mm slack in the cable.
Always use as short a length of cable as necessary. DO NOT EXTEND CABLE. If cable is too short, move other
devices away to create a space for the Quickmov unit(s). Avoid sharp bends in cables.
3.
Connect trimmed cable(s) to neutral bar.
4.
Replace SWB panel and restore power.
EARTHING
For proper operation, all surge diverters rely upon a good earth connection. In some installations the existing earth
system may require upgrading. Important things to look for are that the main earth wire (from earth link on
switchboard to ground rod or system) should preferably be 10mm
2
or greater and must be as short as possible.
Failure to consider the above points can result in improper operation of the unit and possible damage to
the installation.
OPERATION
The status of the Q
UICKMOV
is indicated by a flag visible through the window on the front face of the unit. The flag
changes colour from green to red if the unit is damaged and requires replacement.