background image

For detailed information concerning the operation and features 

available in the PXM4/6/8K Meter Display - 6” Color Touchscreen 

(PXM468K-DISP-6), please refer to PXM4/6/8K Meter Color 

Touchscreen Display Features (IB150004EN) available on the Eaton 

website (www.eaton.com/meters).

Figure 1. PXM4/6/8 Meter and Color Touchscreen Display.

Figure 2. Dimensions of the PXM4/6/8K Meter Display - 6” Color 

Touchscreen (PXM468K-DISP-6).

Installation

1.  Disconnect and lockout all power to the enclosure.
2.  Inspect the enclosure door to determine the best mounting loca-

tion for the PXM4/6/8K Meter Color Touchscreen Display.

otee:

N

A minimum clearance of 2.4 in. (61.0 mm) must be maintained 

between the ventilation holes in the back of the display and any other 

component within the enclosure.

3.  Use the mounting template to mark the cutout area on the enclo-

sure door.  Cut out the marked area.

7.24

(183.9)

0.063~0.240

(1.6~6.1)

5.67

(144.0)

Effective September 2017
Supersedes January 2017

Technical Data 

TD150015EN

PXM4/6/8K Meter Color Touchscreen

Display Quick Start Guide

Figure 3. Cut Out Dimensions.

4.  Ensure proper gasket placement on the PXM4/6/8K Meter Color 

Touchscreen Display.

5.  Insert the PXM4/6/8K Meter Color Touchscreen Display through 

the cutout.  Secure by finger tightening the supplied fasteners.

Figure 4. Mounting the PXM4/6/8K Meter Display.

6.  Check for proper alignment of the PXM4/6/8K Meter Color 

Touchscreen Display then torque fasteners to 6 lb-in. (0.7 N

·

m).

Connections

To use the PXM4/6/8K Meter Color Touchscreen Display, provide  

24 Vdc and connect the power cable between the Color Touchscreen 

Display and the PXM4/6/8K Meter.
The display’s plug-in terminals provide connections for +24 V, 

Common (0), and GND.

6.79

(172.5)

0.12 (3.1) R

Typ.

5.2

(132.1)

Cut Out Dimensions

Summary of Contents for PXM4K Series

Page 1: ...e mounting template to mark the cutout area on the enclo sure door Cut out the marked area 7 24 183 9 0 063 0 240 1 6 6 1 5 67 144 0 Effective September 2017 Supersedes January 2017 Technical Data TD150015EN PXM4 6 8K Meter Color Touchscreen Display Quick Start Guide Figure 3 Cut Out Dimensions 4 Ensure proper gasket placement on the PXM4 6 8K Meter Color Touchscreen Display 5 Insert the PXM4 6 8K...

Page 2: ... 0 1828 8 1 5 38 1 1 5 38 1 Included with the PXM4 6 8K Meter Color Touchscreen Display is a data cable to connect DB9 COM 2 of the Color Touchscreen Display to 3 terminal COM 1 RS485 of the PXM4 6 8K Meter The supplied cables are designed to connect the meter to the PXM4 6 8K Meter Color Touchscreen Display as follows Data cable CM3 Power cable CM4 Figure 6 Meter Web Server Configuration Screen C...

Page 3: ... the side of the meter Figure 7 Changing the PLC Default Station Meter Firmware Requirements The minimum meter firmware version required for compatibility is 13 3 6 1 Technical Information 320 x 234 pixel backlit LCD touch screen display Power 24 Vdc input For meters manufactured prior to November 2015 an exter nal power supply is required for the PXM4 6 8K Meter Color Touchscreen Display Recommen...

Page 4: ... Technical Data TD150015EN Effective September 2017 PXM4 6 8K Meter ColorTouchscreen Display Quick Start Guide EATON www eaton com Figure 8 Cut Out Dimensions Template 6 79 172 5 0 12 3 1 R Typ 5 2 132 1 ...

Page 5: ...5 Technical Data TD150015EN Effective September 2017 PXM4 6 8K Meter ColorTouchscreen Display Quick Start Guide EATON www eaton com Notes ...

Page 6: ...r con tractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR...