Eaton ProtoAir Start-Up Guide
Page 65 of 66
Appendix D Reference
Appendix D.1. Specifications
0F
2
ProtoAir FPA-W34
Electrical Connections
One 3-pin Phoenix connector with: RS-485 (Tx+ / Rx- / gnd)
One 3-pin Phoenix connector with: Power port (+ / - / Frame-gnd)
One Ethernet 10/100 BaseT port
Power Requirements
Input Voltage:
12-24V DC
Current draw:
@ 12V, 240 mA
Power Rating:
2.5 Watts
Approvals
CE and FCC Class B & C Part 15, TUV approved to UL 60950 pending, IC
Canada, RoHS Compliant, PTCRB and CTIA
Power Requirements
12-24V DC
Physical Dimensions
4 x 1.1 x 2.7 in (10.16 x 2.8 x 6.8 cm)
Weight
0.4 lbs (0.2 Kg)
Operating Temperature
-20°C to 70°C (-4°F to158°F)
Humidity
10-95% RH non-condensing
Figure 54: Specifications
Appendix D.1.1. Compliance with UL Regulations
For UL compliance, the following instructions must be met when operating ProtoAir.
The units shall be powered by listed LPS or Class 2 power supply suited to the expected
operating temperature range.
The interconnecting power connector and power cable shall:
o
Comply with local electrical code
o
Be suited to the expected operating temperature range
o
Meet the current and voltage rating for ProtoAir
Furthermore, the interconnecting power cable shall:
o
Be of length not exceeding 3.05m (118.3”)
o
Be constructed of materials rated VW-1, FT-1 or better
If the unit is to be installed in an operating environment with a temperature above 65 °C, it should
be installed in a Restricted Access Area requiring a key or a special tool to gain access.
This device must not be connected to a LAN segment with outdoor wiring.
2
Specifications subject to change without notice