3.6.1.4 Connecting the motor cable
The screened cables between the variable frequency drive and the motor
should be as short as possible.
Figure 41: Connection on motor side
▶
Connect the screening, on both sides and across a large area (360°
overlap), to the protective earth (PE)
.The power screening’s
protective earth (PES) connection should be in the immediate proximity
of the variable frequency drive.and directly on the motor terminal box.
▶
Prevent the screen earth kit from becoming unbraided, i.e. by pushing
the separated plastic covering over the end of the shielding or with a
rubber grommet on the end of the shielding. Terminate the cable screen
across a large area at the end (PES).
Alternatively, you can twist the screen braid and connect it to the
protective earth with a cable lug. In order to prevent EMC interference,
this twisted screen connection should be as short as possible
(recommended value for the twisted cable screen: b
≧
1/5 a).
Figure 42: Screened connection cable in motor circuit
Screened, four-wire cable is recommended for the motor cables. The green-
yellow conductor in these cables must be used to connect the motor’s and
variable frequency drive’s PE terminals, minimizing the loads on the cable
screen (high equalizing currents).