1 Device series
1.4 General rated operational data
DX-NET-DEVICENET
02/14 MN04012005ZEN
www.eaton.com
9
1.4 General rated operational data
Technical Data
Symbol
Unit
Value
General
Standards
meets the requirements of the EN 50178 (standard for electrical safety)
Production quality
RoHS, ISO 9001
Degree of protection
IP20
Interference emissions as per
EN 61000-6-4
Conducted and radiated interference as per EN 55011
Interference immunity EN 61000-6-2:
EN61000-4-2 Electrostatic discharge
EN61000-4-3 Radiated, radio-frequency electromagnetic fields
Fast transient electrical interference/burst as per EN 61000-4-4 Shock waves
as per EN 61000-4-5
EN61000-4-6 Conducted interferences
Environmental conditions
Operating temperature
ϑ
°C
-40 (no hoarfrost) up to +70
Storage temperature
ϑ
°C
-40 - +85
Climatic proofing
p
w
%
< 95, relative humidity, no condensation permitted
Altitude
H
m
max. 1000
Vibration
g
m/s
2
5 – according to IEC 68-2-6
10 - 500 Hz
0.35 mm
DeviceNet connections
power supply
V
3.3
interface
DeviceNet connection via 5-pin screw terminals
data transfer
Automatic baud rate detection
Communication protocol
DeviceNet
IEEE 802.3 according to DS301; DeviceNet adapter (Slave)
Functions
Implicit and Explicit Messaging; UCMM; Change of State;
Cyclic I/O, Polled I/O
Data volume
byte
256 In/Out
Baud rate
kBit/s
125 - 500