7 Accessories
7.1 Device-specific accessories
168
DC1 Variable Frequency Drive
04/16 MN04020003Z-EN
www.eaton.com
7.1.3 DXC-EXT-2RO1AO output expansion
Figure 90: DXC-EXT-2RO1AO
Expansion module DXC-EXT-2RO1AO was developed with HVAC
applications in mind. It can switch the “Drive running” and “Shutdown due
to fault” messages with two separate relays (K1, K2).
Table 35: Specific technical data DXC-EXT-2RO1AO
Technical Specification
Unit
Value
Output switching voltage
K1 (control signal terminals 12, 13)
V
250 AC / 230 DC
K2 (control signal terminals 10, 11)
V
250 AC / 220 DC
AO
V
0 - 10 DC
Relay switching current
K1 (control signal terminals 12, 13)
A
1
K2 (control signal terminals 10, 11)
A
1
AO
mA
< 20
Operating Temperature
°C
-10 - +50
Degree of protection (without the connection
pins being covered by the DC1’s control signal
terminal block)
IP00
→
For detailed instructions on how to install the module, please
refer to instruction leaflet IL04012014Z.
NOTICE
Internal relay K1 is looped with the expansion module, meaning
it can only conduct a lower current (
1 A).
1 2 3 4 5 6 7
8 9 10 11