6 Technical Data
6.2 Specific rated operational data
136
DC1 Variable Frequency Drive
04/16 MN04020003Z-EN
www.eaton.com
6.2.3 DC1-32… device series
Size
Symbol
Unit
2D3
4D3
7D0NN
7D0NB
7D0FB
Rated operational current
I
e
A
2.3
4.3
7
7
Overload current for 60 s every 600 s
i
l
A
3.45
6.45
10.5
10.5
Starting current for 2 s every 20 s
A
4.03
7.53
12.25
12.25
Apparent power at rated operation
230 V
S
kVA
0.92
1.71
2.79
2.79
Apparent power at rated operation
240 V
S
kVA
0.96
1.79
2.91
2.91
Assigned motor power
at 230 V, 50 Hz
P
kW
0.37
0.75
1.5
1.5
at 220 - 240 V, 60 Hz
P
HP
0.5
1
2
2
Power side (primary side):
Number of phases
3
3
3
3
Rated operating voltage
U
LN
V
200 - 10 % - 240 + 10 %, 50/60 Hz
180 - 264 ±0 %, 48 - 62 Hz ±0 %
Input current (phase current)
I
LN
A
3.4
5.6
9.5
8.9
Minimum braking resistance
R
B
Ω
–
–
–
100
Switching frequency (pulse frequency)
Default Setting
f
PWM
kHz
16
16
16
16
Setting range
f
PWM
kHz
4 -32
4 -32
4 -32
4 -32
Maximum leakage current to earth
(PE),
Without motor
I
PE
mA
< 1
< 1
< 1
< 1
Efficiency
η
0.96
0.95
0.96
0.96
Heat dissipation at I
e
(150 %)
P
V
CO
14.8
39.75
61.5
61.5
fan, built-in
–
✓
✓
✓
Size
FS1
FS1
FS1
FS2