3 Control signal terminals
3.2 Configuration of the control signal terminals
DB1 Variable Frequency Drives
09/17 MN040034EN
www.eaton.com
17
3.2.2 P-12 = 1 Digital setpoint, 1 operating direction
Table 10: P-12 = 1: Digital setpoint, 1 operating direction
The setpoint value is set using the keypad = digital setpoint value.
The arrow buttons are used to adjust the setpoint value.
P-15
DI1
(terminal 2)
DI2
(terminal 3)
DI3/AI2
(terminal 4)
DI4/AI1
(terminal 6)
0
START
UP
DOWN
DIR
1
Not permissible
2
FWD
UP
DOWN
Select DIG REF/f-Fix1
3
FWD
UP
EXTFLT
DOWN
4
START
UP
Select DIG REF/AI1 REF
AI1 REF
5
Not permissible
6
START
DIR
EXTFLT
Select DIG REF/f-Fix1
7
FWD
REV
EXTFLT
Select DIG REF/f-Fix1
8
Not permissible
9
Not permissible
10
Not permissible
11
Not permissible
12
Not permissible
13
FWD
No function
EXTFLT
No function
14
Not permissible
15
FWD
Select f-Fix/DIG REF
Select Fire Mode/Normal OP
Select f-Fix4/f-Fix2
16
FWD
Select f-Fix4/DIG REF
Select Fire Mode/Normal OP
DIR
17
FWD
Select DIG REF/f-Fix4
Select Fire Mode/Normal OP
DIR