2 Keypad
2.4 Extended parameter set
DB1 Variable Frequency Drives
09/17 MN040034EN
www.eaton.com
9
2.4 Extended parameter set
Table 5: Enabling and disabling access to the extended parameter set
Commands
Description
Enabling access to the extended parameter set
Press the
OK
button and hold it down for two seconds in
order to access the parameter interface
→
The display will show the parameter that was last
used.
Use the
▲
and
▼
buttons to select parameter P-14
Press the
OK
button.
Use the
▲
and
▼
buttons to enter the password set with
P-37 (default setting: 101)
Press the
OK
button to confirm
→
The extended parameter set (Parameter > P-14 and
display value P00-…) is now available.
Disabling access to the extended parameter set
Use the
▲
and
▼
buttons to set a value for P-14 that
does not match the password (P-37).
Press the
OK
button to confirm
→
Only the “basic parameters,” i.e., parameters P-01 to
P-14, will be available now.
→
The extended parameter set (default setting P-37 = 101)
includes all parameters, from P-01 to P-59.
Additional parameters (up to P-68) can be configured for specific
applications. The password that needs to be entered in P-14 is
equal to the value yielded by P-37 + 100.