5 Technical data
5.6 Mains chokes
DB1 variable frequency drive
11/20 MN040031EN
Eaton.com
104
DX-LN3-…
Figure 54: mains chokes DEX-LN3… (three-phase)
Table 20: Assigned mains chokes (three-phase)
Device type
Input
current
Mains choke, three-phase
(U
LN
max. 500 V +10 %, 50/60 Hz ±10 %)
I
LN
Type
I
e
Type
I
e
A
(max. 50
o
C)
A
(max. 40
o
C)
A
Voltage class: 230 V
Mains voltage: (50/60 Hz) U
LN
: 200 (-10 %) - 240 (+10 %) V
U
e
: 230 V AC, three-phase / U
2
: 230 V AC, three-phase
DB1-322D3FN-N2CC
2.2
DX-LN3-004
3.7
DX-LN3-004
4
DB1-324D3FN-N2CC
4.4
DX-LN3-006
5.7
DX-LN3-006
6
DB1-327D0FN-N2CC
9.6
DX-LN3-016
15.2
DX-LN3-010
10
Voltage class: 400 V
Mains voltage: (50/60 Hz) U
LN
: 380 (-10 %) - 480 (+10 %) V
U
e
: 400 V AC, three-phase / U
2
: 400 V AC, three-phase
DB1-342D2…
2.3
DX-LN3-004
3.7
DX-LN3-004
4
DB1-344D1…
5.6
DX-LN3-006
5.7
DX-LN3-006
6
DB1-345D8…
7.5
DX-LN3-010
9.5
DX-LN3-010
10
DB1-349D5…
10.7
DX-LN3-016
15.2
DX-LN3-016
16