5 Technical data
5.4 Fuses
DB1 variable frequency drive
11/20 MN040031EN
Eaton.com
99
5.4 Fuses
The Eaton circuit-breakers and fuses listed below are examples and can be
used without additional measures.
If you use other circuit-breakers and fuses, make sure to take their protective
characteristics and operational voltage into account. When using other cir-
cuit-breakers, it may be necessary to also use fuses depending on the circuit-
breaker's model, design, and settings. There may also be limitations concer-
ning the short-circuit capacity and the supply mains’ characteristic, and these
must also be taken into account when selecting circuit-breakers and/or
fuses.
Table 16: Safety features
Symbol
Description
①
Miniature circuit breakers
FAZ-B…/1N: 1 pole + N
FAZ-B…/2: 2 pole
FAZ-B…/3: 3 pole
Rated operating voltage: 230/400 V AC
Switching capacity: 15 kA
②
Motor-Protective Circuit-Breakers
PKM0…, PKZM4…: 3 pole
Rated operating voltage: 690 V AC
Switching capacity:
• PKM0: 150 kA to 12 A and 50 kA to 32 A
• PKZM4: 50 kA
③
Fuse
Rated operating voltage: 500 V AC
Switching capacity: 50 kA
Frame size: DII, E27 / DIII, E33
Fuse base: S27, S33
④
Fuse Class J
Rated operating voltage: 600 V AC
Switching capacity: 300 kA
Fuse Bases:
• up to 30 A: J60030…
• 35 - 60 A: J60060…
• 70 - 100 A: JM60100…