2 Engineering
2.8 Sine wave filters
62
DA1 Variable Frequency Drives
08/18 MN04020005Z-EN
www.eaton.com
2.8 Sine wave filters
TheDX-SIN3… sine wave filter removes high-frequency components from
the variable frequency drive’s output voltage (U
2
). This reduces the
conducted and radiated emission. The output voltage of the sine wave filter
reaches a sinusoidal shape with a lower overlapped output ripple.
The distortion factor of the sine wave voltage is typically 5 % to 10 %.
This reduces the noise generation and losses in the motor.
Figure 35:Maximum permissible motor cable lengths
a
Screened motor cable:
U
2
≦
230 V
→
l
≦
200 m; U
2
≦
500 V
→
l
≦
150 m
unscreened motor cable: U
2
≦
230 V
→
l
≦
300 m; U
2
≦
500 V
→
l
≦
200 m
→
The DX-SIN3… sine wave filters are not permitted to be
operated with a lower frequency than the switching frequency
stated on the sine wave filter .
For this, the P6-02 parameter (“auto-temperature-manage-
ment”) needs to be set to the double value of the switching
frequency set on the sine wave filter.
Permissible switching frequencies (P2-24) for DA1 with
DX-SIN3…: 1
≙
8 kHz; 2
≙
12 kHz
For the DA1 variable frequency drive, the set value with the
double-modulation procedure is the double value of the
effective value in the sine wave filter (1
≙
8 kHz
→
4 kHz;
2
≙
12 kHz
→
6 kHz).
→
For the rated sine wave filters for DA1 variable frequency drives,
please refer to the technical data chapter in
M
3 ~
DX-SIN3...
f
PWM
f
2
U
2
l
e
u
k
l
①
L
Motor
Mains