3 Installation
3.7 Block diagrams
124
DA1 Variable Frequency Drives
08/18 MN04020005Z-EN
www.eaton.com
3.7.2 DA1-…-B55C
Figure 91: DA1-…-B55C block diagram
①
Direct enable of the STO function or relay: Safe Torque Off (STO),
SIL 2 (EN 61800-5-2)
②
The RFI filter is not contained in the DA1-35-…-B6XC device.
③
A DC link choke is contained in sizes FS5, FS6, FS7.
Type
Mains
Motor
Voltage U
LN
Frequency f
LN
Voltage U
2
Frequency f
2
DA1-32-…-B55C
3~ 200 V (-10%) - 240 V (+10%)
50/60 Hz
3~ 230 V
0 - 500 Hz
DA1-34-…-B55C
3~ 380 V (-10%) - 480 V (+10%)
50/60 Hz
3~ 400 V/ 460 V 0 - 500 Hz
DA1-35-…-B55C
3~ 500 V (-10%) - 600 V (+10%)
50/60 Hz
3~ 500 V/ 575 V 0 - 500 Hz
BR
PE
W
V
U
M
3 ~
13
STO-
1
+24 V Out
< 100 mA
24 V
2
DI1
FWD
REV
FF1/FF2
FF2
3
DI2
4
DI3
10
DI5
(AI2)
12
STO+
5
+10 V Out
< 10 mA
6
AI1
(DI4)
0 V
7
CPU
STO
10 V
0 V
f-Soll
0…+10 V
PES
+
-
15
16
Error
RUN
17
18
11
14
8
9
6 A, 250 V AC
5 A, 30 V DC
6 A, 250 V AC
5 A, 30 V DC
A-Out
0 V
0 V
K11
K14
K12
K23
K24
AO2
(DO2)
AO1
(DO1)
f-Out
L1
L3
L2
3 ~
0…10 V, 0/4… 20 mA
+24 V
< 10 mA
RS485
X1
Modbus RTU
CANopen
OP-Bus
DC+
DC-
R
B
①
②
③
→
The STO connection must be made by the user.
→
The VAR screw cannot be disabled with devices in sizes FS4,
FS5, FS6 and FS7.