EATON
Powerware
®
225 kVA PDU Installation and Operation Manual
S
164201629 Rev D
www.powerware.com
1−1
Chapter 1
Introduction
The Eaton
®
Powerware
®
225 kVA Three−Phase Power Distribution Unit (PDU) is
designed for use with all three−phase uninterruptible power systems and three−phase
power sources. The PDU provides power distribution, voltage transformation,
metering, status monitoring, and load profiling with easy adaptation and expansion
without costly electrical rework.
The PDU is housed in a single, free-standing cabinet, with safety shields behind the
doors for hazardous voltage protection. Figure 1-1 through Figure 1-3 show the
Powerware 225 kVA Three−Phase Power Distribution Unit.
NOTE
Startup and operational checks must be performed by an authorized Eaton Customer Service
Engineer, or the warranty terms specified on page 10−1 become void. This service is offered as part of the
sales contract for the UPS. Contact an Eaton service representative in advance (usually a two−week notice is
required) to reserve a preferred startup date.
1.1
PDU Standard Features
The PDU has the following standard features that provide cost-effective and
consistently reliable power distribution.
1.1.1
Control Panel
The control panel, located on the front of the PDU, contains an LCD panel and
pushbutton switches to control the operation and to display the status of the PDU.
See Chapter 6, PDU Operating Instructions," for additional information.
1.1.2
Power Monitoring
The PDU provides the following monitoring features:
S
PDU status and event log recording
S
PDU metering for the following:
−
Input voltages – phase to phase
−
Output voltages – phase to phase and phase to neutral
−
Output current
−
kVA, kW, frequency, ground current, and power factor
−
Percent loading per phase
S
Load profiling
−
Minimum and maximum voltage, current, frequency, and kilowatt
−
Highest reading on a monthly basis
See Chapter 6, PDU Operating Instructions," for additional information.