3.3 Inspecting and unpacking the UPS cabinet
The UPS cabinet is palleted separately for shipping. The cabinet is shipped bolted to a wooden pallet
and protected with outer protective packaging material (see Figure 3-8).
WARNING
The UPS cabinet is heavy (see Table 3-1 on page 12). If unpacking instructions are not closely
followed, the cabinet may tip and cause serious injury and equipment damage.
Do not install a damaged cabinet. Report any damage to the carrier and contact your service
representative immediately.
1.
Carefully inspect the outer packaging for evidence of damage during transit.
NOTE
For the following step, verify that the forklift or pallet jack is rated to handle the weight of the
cabinet (see Table 3-1 on page 12 for cabinet weight).
2.
Use a forklift or pallet jack to move the packaged cabinet to the installation site, or as close as
possible, before unpacking. Insert the forklift or pallet jack forks from the right side of the cabinet,
between the supports on the bottom of the pallet (see Figure 3-8 on page 26 for the location of
the UPS center of gravity).
WARNING
Do not tilt the UPS cabinet more than 10° from vertical or the cabinet may tip over.
3.
Set the pallet on a firm, level surface, allowing a minimum clearance of 3 m on each side for
removing the cabinet from the pallet.
NOTE
The UPS cabinet is shipped with a debris shield covering the ventilation grill on top of the unit.
Do not remove the debris shield until installation is complete.
4.
Remove the protective covering from the cabinet.
5.
Remove the packing material, and discard or recycle in a responsible manner.
6.
After removing the protective covering, inspect the contents for any evidence of physical damage,
and compare each item with the Bill of Lading. If damage has occurred or shortages are evident,
contact your service representative immediately to determine the extent of the damage and its
impact upon further installation.
Summary of Contents for Power Xpert 9395P
Page 1: ...User s and Installation Guide Power Xpert 9395P UPS 500 kVA 600 kVA P 164000476 ...
Page 2: ...P 164000476 9395P 500kVA 600 kVA 2 Revision 002 User s and Installation Guide ...
Page 18: ...P 164000476 9395P 500kVA 600 kVA 8 Revision 002 User s and Installation Guide ...
Page 37: ...P 164000476 9395P 500kVA 600 kVA 27 Revision 002 User s and Installation Guide ...