P-164000476
9395P 500kVA / 600 kVA
13
Revision 002
User’s and Installation Guide
Table 3-3: Air conditioning or ventilation requirements during full load operation
Ventilation required for cooling air exhaust: approximately 920 liter/sec/250-300kVA unit, + 280 liter/sec
(ISBM).
Figure 3-1. UPS cabinet dimensions (front view)
Rating/kVA
Heat rejection
kW
Heat rejection
BTU / h x 1000
500 kVA
19.8
67.6
600 kVA
25.5
87.0
1882
1874
18
74
1878