![Eaton Power Xpert 9395P User And Installation Manual Download Page 11](http://html.mh-extra.com/html/eaton/power-xpert-9395p/power-xpert-9395p_user-and-installation-manual_525137011.webp)
P-164000476
9395P 500kVA / 600 kVA
1
Revision 002
User’s and Installation Guide
1 Introduction
The Eaton Power Xpert ® 9395P uninterruptible power supply (UPS) is a true online, continuous-duty,
transformerless, double-conversion, solid-state, three-phase system, providing conditioned and
uninterruptible AC power to protect the customer’s load from power failures.
The Eaton 9395P UPS 500 kVA PF 1.0 and 600 kVA PF 0.92 contains two sections: a section configured
either as an integrated system bypass module (ISBM) or an Input Output Module (IOM) rated for a
maximum of 500/600 kVA and an Uninterruptible Power Module (UPM) section containing two UPMs.
Each UPM is rated for a maximum of 250 kVA / 300 kVA for a total maximum of 500 kVA / 600 kVA.
The UPS is available as a single unit or as an optional multiple unit distributed bypass system (see
Section 1.2.6).
The Eaton online power protection system is used to prevent loss of valuable electronic information,
minimize equipment downtime, and minimize the adverse effect on production equipment due to
unexpected power problems.
The Eaton 9395P UPS continually monitors incoming electrical power and removes the surges, spikes,
sags, and other irregularities that are inherent in commercial utility power. Working with a building’s
electrical system, the UPS system supplies clean, consistent power that sensitive electronic
equipment requires for reliable operation. During brownouts, blackouts, and other power interruptions,
batteries provide emergency power to safeguard operation.
The UPS system is housed in a single, free-standing cabinet with safety shields behind the door for
hazardous voltage protection. The cabinet matches the battery and distribution cabinets in style and
color and can be installed in line-up-and-match or standalone configurations.
Figure 1-1 shows the Eaton 9395P UPS 500 kVA / 600 kVA.
NOTE
Startup and operational checks must be performed by an authorized Eaton Customer Service
Engineer, or the warranty terms specified on page 136 become void. This service is offered as
part of the sales contract for the UPS. Contact service in advance (usually a two-week notice is
required) to reserve a preferred startup date.
1.1 UPS standard features
The UPS has many standard features that provide cost-effective and consistently reliable power
protection. The descriptions in this section provide a brief overview of the UPS standard features.
1.1.1 Installation features
Cabinets can be permanently bolted to the floor. Power and control wiring can be routed through the
top or bottom of the cabinet with connections made to easily accessible terminals. Line-up-and-match
battery cabinets are wired through the side panels of the units. Optional X-Slot connectivity cards are
quickly installed at the front of the unit and are hot-pluggable.
1.1.2 Control panel
The control panel, located on the front of the UPS, is a 7” touchscreen to control the operation of the
UPS and to display the status of the UPS system. See Chapter 7: “UPS operating instructions” for
additional information.
The following figure shows the Eaton 9395P UPS with the 7” LCD Color Touchscreen.
Summary of Contents for Power Xpert 9395P
Page 1: ...User s and Installation Guide Power Xpert 9395P UPS 500 kVA 600 kVA P 164000476 ...
Page 2: ...P 164000476 9395P 500kVA 600 kVA 2 Revision 002 User s and Installation Guide ...
Page 18: ...P 164000476 9395P 500kVA 600 kVA 8 Revision 002 User s and Installation Guide ...
Page 37: ...P 164000476 9395P 500kVA 600 kVA 27 Revision 002 User s and Installation Guide ...