Chapter 8
Communication
This chapter describes the communication features of the Eaton Power Xpert 9395P-900 UPS system and
provides information about connecting hardware. For terminal wiring information, see paragraph and paragraph
4.7. For location of the customer interface panels and terminals, see Figure 4-16 and Figure 4-21 through
Figure 4-24.
8.1
X-Slot Cards
l
Power Xpert
®
Gateway Card - provides a data gateway from the UPS to the Power Xpert software; provides
remote monitoring through a Web browser interface, e-mail, and a network management system using
SNMP; connects to a twisted-pair Ethernet (10/100BaseT) network. Modbus TCP support provides direct
integration of the UPS parameters to a Building Management System (BMS). It has a built-in switching hub
that allows one additional network device to be connected to the network without the requirement of an
additional network drop.
l
Modbus Card - provides direct integration of UPS information (meters and status) to a Building Management
System (BMS) using the Modbus RTU protocol.
l
Relay Interface Card (AS/400) - has isolated dry contact (Form-C) relay outputs for UPS status: Utility failure,
Low battery, UPS alarm/OK, or On bypass when interfacing with IBM AS/400 computers, other relay
connected computers, and industrial applications.
l
Industrial Relay Card (IRC) - indicates the operating status of the UPS system using the customer's
monitoring equipment. The IRC uses four isolated normally-open or normally-closed dry relay contacts to
indicate the UPS status. Online, Bypass, Battery, and Alarm modes can be monitored.
l
Hot Sync CAN Bridge Card - provides connectivity for operational mode control and metering of a parallel
system at any UPM in the system. In addition, this card can be used to connect optional system monitoring
devices, such as a Remote Monitor Panel II (RMP II), a Relay Interface Module II (RIM II), or a Supervisory
Contact Module II (SCM II) to the UPS.
LAN drops for use with X-Slot connectivity cards must be provided by facility planners or the customer.
For installation and setup of an X-Slot card, contact an Eaton service representative (see page 1-10). Refer to
the manual supplied with the X-Slot card for user instructions.
Figure 8-1. Optional X-Slot Cards
Relay Interface Card
Modbus Card
Hot Sync CAN Bridge
Card
Industrial Relay Card
Power Xpert Gateway Card