9395P-600 (300V-600V) Installation and Operation Manual 164000710—Rev 07
77..44
U
UP
PS
S O
Oppeerraattiioonn uussiinngg tthhee C
Coolloorr TToouucchhssccrreeeenn C
Coonnttrrooll P
Paanneell
NOTE
The Energy Saver System mode commands are displayed only if installed at the factory
or by an Eaton Customer Service Engineer.
NOTE
The Variable Module Management System and Energy Saver System modes are
mutually exclusive. If the Variable Module Management System mode is enabled, the
Energy Saver System mode commands will not be displayed.
NOTE
If the touch screen fails to respond, open the front door and depress the RESET button
located on the bottom of the screen mounting assembly. The screen will reboot but
NOT affect system status or operation.
77..44..11
S
Sttaarrttiinngg tthhee U
UP
PS
S iinn O
Onnlliinnee M
Mooddee
To start the UPS system:
1.
Unfasten the front door latch and swing the door open (refer to 9395 UPS Operation and Installation
manual supplied with system).
NOTE
*Only perform steps 2 and 5 if the UPS has an input breaker CB1 (see
2.
*Verify that input breaker CB1 is open.
3.
Close the UPS input feeder circuit breaker.
4.
Close the UPS Bypass input feeder circuit breaker.
5.
*Close input breaker CB1.
6.
Close the door and secure the latch.
7.
Observe the UPS control panel display becoming active, indicating logic power.
8.
Press the
LOCK
icon on the main screen. The Sign In screen is displayed. Use operator password to log in
(factory default password is
0101
).
9.
On the System screen, verify the UPS status is OK and the
UPM
status is
OFFLINE
.
10. Close the battery breaker.
11. Verify no alarms are active on the
EVENTS LOG
screen.
12. On the System Status screen, select the
UPS CONTROLS
command.
13. On the UPS Control Command screen, select
GO ONLINE
.
If Auto Bypass is enabled (factory default), the critical load is immediately supplied by the bypass source, in
Bypass mode, until the inverter turns on and the UPS transfers to Online mode. The status indicator on the
UPS control panel indicates the UPS is in Bypass mode. If Auto Bypass is not enabled, the UPS output
remains off until the UPS transfers to Online mode.
14. The
UPS START UP
screen appears
The rectifier and inverter turn on. The inverter continues to ramp up to full voltage.
When the inverter reaches full voltage, the UPS output contactor K3 closes and the static switch turns off.
Power is now supplied to the critical load in Online mode. It takes approximately one minute for the UPS to
achieve Online mode.
The Online status indicator is illuminated. The UPS status indicates
ONLINE
on the header section of the
screen. The UPM status indicates
ONLINE
,
CHARGING
on the MIMIC Screen.