
68
Eaton
®
Power Xpert
®
9395P-1200 Installation and Operation Manual 164000500—Rev 11
44..55
FFiieelldd IInnssttaalllleedd U
UP
PM
M IInnssttaallllaattiioonn
If installing a Plus 1 configuration with an FI-UPM, install the FI-UPM using the instructions in the
Eaton®
Power Xpert® 9395P UPS Field Installed UPM Mechanical Installation Manual
(P-164000503) listed in
. After the FI-UPM is installed, proceed to
in this
document if installing a battery system; otherwise, proceed to
Installing UPS External and Battery Power Wiring
in this document to complete the wiring of the UPS.
44..66
B
Baatttteerryy S
Syysstteem
m IInnssttaallllaattiioonn
If installing a battery system, install the customer-supplied battery system according to the battery and battery
system manufacturer's instructions and all applicable codes and regulations, including the NEC, Article 480.
After the battery system is installed, proceed to paragraph
Distributed Bypass Tie Cabinet Installation
if
installing a distributed bypass tie cabinet; otherwise, proceed to paragraph
Installing UPS External and Battery Power Wiring
to complete the wiring of the UPS.
44..77
D
Diissttrriibbuutteedd B
Byyppaassss TTiiee C
Caabbiinneett IInnssttaallllaattiioonn
NOTE
The tie cabinet must contain Module Output Breakers (MOBs) with dual auxiliary
contacts for control of the system. Without dual auxiliary MOBs, UPMs are not allowed
to go to bypass individually during servicing. All UPMs will go to bypass instead of the
just the UPM needing service, decreasing critical load protection. With dual auxiliary
MOBs, one UPM can be bypassed while the remaining UPMs support the load as long
as the remaining UPMs have the capacity to do so.
If installing a distributed bypass system, install the customer-supplied tie cabinet or distribution panel according
to the tie cabinet or distribution panel manufacturer's instructions and all applicable codes and regulations,
including the NEC, Article 480. After the tie cabinet is installed, proceed to paragraph
Installing UPS External and Battery Power Wiring
to complete the wiring of the UPS.
44..88
IInnssttaalllliinngg U
UP
PS
S EExxtteerrnnaall aanndd B
Baatttteerryy P
Poow
weerr W
Wiirriinngg
NOTE 1
The ISBM and UPM sections are shipped with debris shields covering the ventilation
grills on top of the sections (see
). Do not remove the debris shields until
installation is complete. However, remove the shields before operating the UPS. Once
the debris shields are removed, do not place objects on the ventilation grills.
NOTE 2
Remove the ISBM section top or bottom conduit landing plate to drill or punch conduit
holes (see
Remove the ISBM section top or bottom conduit landing plate to drill or punch conduit holes (see
44..88..11
EExxtteerrnnaall P
Poow
weerr W
Wiirriinngg IInnssttaallllaattiioonn
To install wiring to connections:
1.
Remove one top screw and two bottom screws securing each ISBM section left and right front panel (see
UPS System Power Wiring Preparation
). Lift the panels straight up to remove them from the panel
hanger brackets at the top of the cabinet.
2.
Remove the screws securing the top and bottom internal safety shield panels and remove the panels to
gain access to the input, output, and battery terminals. Retain the hardware for later use.
3.
Route the input and output cables through either the top or bottom of the cabinet to the UPS terminals.
See
through
for wiring access information and terminal locations.
Top Access Wiring
. Remove the top conduit plate from the top of the ISBM section. Identify all conduit
requirements and mark their location. Drill and punch all conduit holes in the top conduit plate prior to
Summary of Contents for Power Xpert 9395P-1100/1100
Page 8: ......
Page 214: ...16400050011 164000500 11...