38
Eaton
®
Power Xpert
®
9395P-1200 Installation and Operation Manual 164000500—Rev 11
Table 16. UPS Intercabinet Power Cable Terminations for the Three/Four UPM Models
Terminal Function
Terminal
Function
Bus Landing
Tightening
Torque
Nm (lb ft)
Stud
AC Input to UPM
Section
E1A (UPM 1)
E1A (UPM 2)
E1A (UPM 3)
E1A (UPM 4) – Four UPM Model
Phase A
4 – 2 stud mounting
14.2 (10.4)
M8
E2A (UPM 1)
E2A (UPM 2)
E2A (UPM 3)
E2A (UPM 4) – Four UPM Model
Phase B
4 – 2 stud mounting
14.2 (10.4)
M8
E3A (UPM 1)
E3A (UPM 2)
E3A (UPM 3)
E3A (UPM 4) – Four UPM Model
Phase C
4 – 2 stud mounting
14.2 (10.4)
M8
AC Output from UPM
Section
E9A (UPM 1)
E9A (UPM 2)
E9A (UPM 3)
E9A (UPM 4)
Phase A
4 – 2 stud mounting
14.2 (10.4)
M8
E10A (UPM 1)
E10A (UPM 2)
E10A (UPM 3)
E10A (UPM 4)
Phase B
4 – 2 stud mounting
14.2 (10.4)
M8
E11A (UPM 1)
E11A (UPM 2)
E11A (UPM 3)
E11A (UPM 4)
Phase C
4 – 2 stud mounting
14.2 (10.4)
M8
E12A (UPM 1)
E12A (UPM 2)
E12A (UPM 3)
E12A (UPM 4)
Neutral
4 – 2 stud mounting
14.2 (10.4)
M8
DC Input to UPM
Section
1E4A (UPM 1)
2E4A (UPM 2)
3E4A (UPM 3)
3E4A (UPM 4)
Positive
6–stud mounting
(2 per UPM)
14.2 (10.4)
M8
1E5A (UPM 1)
2E5A (UPM 2)
3E5A (UPM 3)
3E5A (UPM 4)
Negative
6–stud mounting
(2 per UPM)
14.2 (10.4)
M8
Summary of Contents for Power Xpert 9395P-1100/1100
Page 8: ......
Page 214: ...16400050011 164000500 11...