Eaton
®
Power Xpert
®
9395P-1200 Installation and Operation Manual 164000500—Rev 11
17
•
The system must be installed in a temperature and humidity controlled indoor area free of conductive
contaminants.
•
The cabinet can be installed in
line-up-and-match
or
standalone
configurations.
Failure to follow guidelines may void your warranty.
The UPS equipment operating environment must meet the weight requirements shown in
and the size
requirements shown in
through
. Dimensions are in millimeters (inches).
includes the weights of the heaviest cabinet configuration. Actual weights may be less due to installed
configuration. Weights are in kilograms (pounds).
Table 2. UPS Cabinet Maximum Weights
Model
Section
Maximum Weight kg (lb)
Shipping
Installed
Power Xpert 9395P-1200/1200
Power Xpert 9395P-1200/1100
Power Xpert 9395P-1200/1000
ISBM (CSS)
952 (2099)
908 (2002)
3XUPM
1667 (3675)
1620 (3571)
FI-UPM
500 (1102)
475 (1047)
Power Xpert 9395P-1200/900
Power Xpert 9395P-1200/825
Power Xpert 9395P-1200/750
Power Xpert 9395P-1200/675
ISBM (CSS)
952 (2099)
908 (2002)
3XUPM
1667 (3675)
1620 (3571)
NOTE CSS = Continuous Static Switch
The UPS cabinets use forced air cooling to regulate internal component temperature. Air inlets are in the front
of the cabinet and outlets are in the top. Allow clearance in front of and above each cabinet for proper air
circulation. The clearances required around the UPS cabinet are shown in
. Dimensions are in
millimeters (inches).
Table 3. UPS Cabinet Clearances
From Top of Cabinet
457.2 mm (18") minimum clearance for ventilation
From Front of Cabinet
914.4 mm (36") working space
From Back of Cabinet
None Required
From Right Side of Cabinet
None Required
From Left Side of Cabinet
None Required
The basic environmental requirements for operation of the UPS are:
•
Ambient Temperature Range:
–
ALL RATINGS EXCEPT 1200 kW, 900 kW: 0–40º C (32–104º F)
–
For 1200 kW, 900 kW: 0–35°C (32–95°F) at elevations up to 1000 m without derating.
•
Recommended Operating Range: 20–25º C (68–77º F)
•
Maximum Relative Humidity: 95%, non-condensing